User Manual

Technical data
300 IDEC SmartRelay Manual
Input current at
Signal 0
Signal 1
Signal 0
Signal 1
< 0.03 mA AC
> 0.08 mA AC
< 0.03 mA DC
> 0.12 mA DC
Delay time at
0 to 1 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
1 to 0 : 120 V AC
: 240 V AC
: 120 V DC
: 240 V DC
typ. 50 ms
typ. 30 ms
typ. 25 ms
typ. 15 ms
typ. 65 ms
typ. 105 ms
typ. 95 ms
typ. 125 ms
Line length (unshielded) 100 m
Digital outputs
Number 4
Output type Relay outputs
Electrical isolation Yes
Dielectric Strength
(between power/input terminals and
output terminals)
2,500 V AC, 1minute
500 V DC, 1 minute
In groups of 1
Control of a digital input Yes
Continuous current I
th
max. 10 A per relay
Surge current max. 30 A
Incandescent lamp load (25000 switching
cycles) at
230/240 V AC
100/110 V AC
1000 W
500 W
Fluorescent tubes with ballast (25000
switching cycles)
10 x 58 W (at 230/240 V AC)
Fluorescent tubes, conventionally
compensated (25000 switching cycles)
1 x 58 W (at 230/240 V AC)
Fluorescent tubes, uncompensated
(25000 switching cycles)
10 x 58 W (at 230/240 V AC)
Short circuit–proof cos 1 Power protection B16, 600A
Short circuit-proof cos 0.5 to 0.7 Power protection B16, 900A
Derating none; across the entire temperature range
Parallel output circuits for power increase Not permitted
Protection of output relay (if desired) max. 16 A, characteristic B16
FL1E-H12RCC
FL1E-B12RCC