IDEC SmartRelay functions
IDEC SmartRelay Manual 183
Analog comparator (actual value Ax - Ay, see Chapter
4.4.18)
Analog trigger (actual value Ax, see Chapter 4.4.16)
Analog amplifier (actual value Ax, see Chapter 4.4.20)
Analog multiplexer (actual value AQ, see Chapter 4.4.26)
Analog ramp control (actual value AQ, see Chapter
4.4.27)
Analog math (actual value AQ, see Chapter 4.4.30)
PI controller (actual value AQ, see Chapter 4.4.28)
Up/down counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number.
Parameter p (number of
decimals)
Applies only to the Aen, Ax,
1
and
2
values displayed in a
message text.
Timing diagram
Q
Aen +
1
Ax
En
Aen –
2
Aen
Functional description
A 0 to 1 transition at input En saves the value of the signal at
th
e analog input Ax. This saved process variable is referred
to as ”Aen”.
Both the analog actual values Ax an
d Aen are multiplied by
the value at parameter A (gain), and parameter B (offset) is
then added to the product:
(Axgain) + offset = Actual value Aen, when input En
chan
ges from 0 to 1, or
(Axgain) + offset = Actual value Ax.
Output Q is set when the signal at input En = 1 and if the
actual valu
e at input Ax is out of range of
Aen -
2
to Aen +
1
.
Output Q is reset, when the actual value at input Ax lies
wit
hin the range of
Aen -
2
to Aen+
1
, or when the signal at
input En changes to lo.