IDEC SmartRelay functions
178 IDEC SmartRelay Manual
Parameter p (number of decimals)
Does not apply to Ax, Ay, On, Off and values displayed in
a message text.
Does not apply to the comparison of on and off values! (The
com
pare function ignores the decimal point.)
Q
for Ax - Ay > 200,
if On = Off = 200
Ax
1000
0
Ay
1000
0
Ax - Ay
1000
0
200
Timing diagram
Functional description
The function fetches the analog values from the inputs Ax
an
d Ay.
Ax and Ay are each multiplied by the value of the A (gain)
p
arameter, and the value at parameter B (offset) is then
added to the relevant product, i.e.
(Ax•gain) + offset = actual value Ax or
(Ay•gain) + offset = actual value Ay.
The function forms the difference (””) between the actual
values Ax - Ay.
Output Q is set or reset, depending on difference of the
a
ctual values Ax - Ay and the set thresholds. See the
calculation rule below.
Calculation rule
If the On threshold Off threshold, then:
Q = 1, if:
(actual value Ax - actual value Ay) > On
Q = 0, if:
(actual value Ax - actual value Ay) Off.
If the On threshold < Off thr
eshold, then Q = 1, if:
On (actual value Ax - actual value Ay) < Off.