Parameter T
Note the defaults for parameter T in Chapter 4.3.2.
The time for parameter T can also be preset based on the
a
ctual value of another, already-configured function. You
can use the actual values of the following functions:
Analog comparator (actual value Ax - Ay, see Chapter
4.4.18)
Analog trigger (actual value Ax, see Chapter 4.4.16)
Analog amplifier (actual value Ax, see Chapter 4.4.20)
Analog multiplexer (actual value AQ,
see Chapter 4.4.26)
Analog ramp control (actual value AQ, see Chapter
4.4.27)
Analog math (actual value AQ, see Chapter 4.4.30)
PI controller (actual va
lue AQ, see Chapter 4.4.28)
Counter (actual value Cnt, see Chapter 4.4.13)
Select the required function by the block number. The
time
base is adjustable. Please note the following listing:
Valid ranges of the timebase, if T = parameter
The display in programming mode (example):
B12 +R
T =04:10h
Valid ranges of the timebase, if T = Actual value of an already-
programmed function
Timebase max. value min. resolution Accuracy
s (seconds) 99:99 10 ms +
10 ms
m (minutes) 99:59 1s +
1 s
h (hours) 99:59 1 min + 1 min
Timebase max. value Meaning Accuracy
ms 99990 Number of ms + 10 ms
s 5999 Number of s +
1 s
m 5999 Number of min +
1 min