Product Manual
23
TP10KAC-DX
July 2017
Fig. 14b (Rear Arm)
15. Filling Reservoir Tank
.
A. Remove the fill level screw of the power unit tank. Fill it with Non-Detergent / Non-Foaming
Hydraulic Oil - SAE-10, AW 32 or equivalent, until fluid reaches the bottom of the screw hole.
Replace the fill screw.
16. Lubricate the four inside corners of both columns with heavy duty grease.
17. Electrical Connection to Power Unit & Overhead Limit Switch
A. Have a certified electrician make the electrical connection from power supply to the power unit. Use
separate circuit for each power unit, as shown below in (Fig. 15).
B. Have a certified electrician make the electrical connection for the overhead limit switch to power unit’s
switch box, as shown in (Fig. 15).
Fig. 15
Electrical Wiring must comply with local code. Protect each circuit with time delay fuse or
circuit breaker. For 208V-230V single phase, use 20 amp fuse.
Never operate the motor in line voltage less than 208VAC as motor damage may occur.
Limit Bolt / Nut