Instructions / Assembly
* Follow the proper connection as shown in Fig. 1. The LED (red) indicator
will light. This indicates that a correct current flow is taking place.
Battery replacement:
When the symbol “ “ appears on the display, replace with new batteries as follows:
• Disconnect the test leads from the instrument and turn off the power.
• Unscrew the cover, then slide the cover, take out the batteries and replace with new
batteries, type AA.
• Replace back cover and secure with 2 screws.
• If the meter is not to be used for periods of longer than 60 days, remove the batteries
and store them separately.
Maintenance:
Clean the case with a damp cloth and mild detergent : do not use abrasives or solvents.
Service and Replacement Parts:
This unit has no user-serviceable parts.
For replacement parts or to inquire about service information, contact IDEAL INDUSTRIES, INC.
at 1-877-201-9005 or visit our website www.testersandmeters.com.
SPECIFICATIONS
Measurement System: Operating Frequency - 820Hz, 2mA approx.
Earth resistance: Range: 20/200/2000Ω
Resolution: 0~19.99Ω (0.01Ω)
0~199.9Ω (0.1Ω)
0~1999Ω (1Ω)
Earth voltage: 0~200V AC, 40-500Hz
Accuracy: Earth resistance: ±(2%reading± 2digits) or ±0.1Ω,
whichever is greater.
Earth voltage: ±(1% reading±2digits)
Display: LCD 3½ digit (2000 counts)
Low battery indication: “ ”Symbol appears on the display.
Data hold indication: “ ” Symbol appears on the display.
Over range indication: “ 1 ” (MSD).
Safety standard: IEC/EN 61010-1, Installation CATIII - 200V.
Power source: (8) 1.5V (AA) batteries required.
Dimensions: 8.3”Hx8.3”Wx4.0”D (210mmLx210mmWx100mmD)
Weight: Approx. 3 Lbs(1361g) (batteries included).
Accessories included: Hard Case, Test leads (red-33m, yellow-33m, green-5m), 2 Auxiliary
earth spikes, simplified measurement probe, Instruction manual.
HOLD
3