Instructions / Assembly

* Follow the proper connection as shown in Fig. 1. The LED (red) indicator
will light. This indicates that a correct current flow is taking place.
Battery replacement:
When the symbol “ “ appears on the display, replace with new batteries as follows:
Disconnect the test leads from the instrument and turn off the power.
Unscrew the cover, then slide the cover, take out the batteries and replace with new
batteries, type AA.
Replace back cover and secure with 2 screws.
If the meter is not to be used for periods of longer than 60 days, remove the batteries
and store them separately.
Maintenance:
Clean the case with a damp cloth and mild detergent : do not use abrasives or solvents.
Service and Replacement Parts:
This unit has no user-serviceable parts.
For replacement parts or to inquire about service information, contact IDEAL INDUSTRIES, INC.
at 1-877-201-9005 or visit our website www.testersandmeters.com.
SPECIFICATIONS
Measurement System: Operating Frequency - 820Hz, 2mA approx.
Earth resistance: Range: 20/200/2000Ω
Resolution: 0~19.99Ω (0.01Ω)
0~199.9Ω (0.1Ω)
0~1999Ω (1Ω)
Earth voltage: 0~200V AC, 40-500Hz
Accuracy: Earth resistance: ±(2%reading± 2digits) or ±0.1Ω,
whichever is greater.
Earth voltage: ±(1% reading±2digits)
Display: LCD 3½ digit (2000 counts)
Low battery indication: “ ”Symbol appears on the display.
Data hold indication: “ ” Symbol appears on the display.
Over range indication: “ 1 ” (MSD).
Safety standard: IEC/EN 61010-1, Installation CATIII - 200V.
Power source: (8) 1.5V (AA) batteries required.
Dimensions: 8.3”Hx8.3”Wx4.0”D (210mmLx210mmWx100mmD)
Weight: Approx. 3 Lbs(1361g) (batteries included).
Accessories included: Hard Case, Test leads (red-33m, yellow-33m, green-5m), 2 Auxiliary
earth spikes, simplified measurement probe, Instruction manual.
HOLD
3