Full Product Manual

Document: September1, 2009 Page 7of 10
A comparison of the Standardized Measured Values to the SureTest Readings should
yield results in accordance to the range and accuracy specification listed in Table 2.
Table 3, Standardized Data
Measured Value SureTest Reading
AC Line Voltage
V V
AC Peak Voltage
V V
AC line Frequency
Hz Hz
% Voltage Drop 12A
% %
% Voltage Drop 15A
% %
% Voltage Drop 20A
% %
Neutral to Ground V V V
Hot Conductor
Neutral Conductor
Ground Conductor
Table 4 illustrates how to combine the branch circuit measured values with the
specifications from Table 2 to create a table of values between which the SureTest
reading should fall between to verify that it is with calibration.
Table 4, Example of Field tested
Field Test for 61-164/61-
165
Enter
SureTest
Function
Measured
Values Specification count % error Low Limit High Limit Readings
AC Line 122.00 1% +/- 1 digit 0.10 0.010 120.68 123.32 121.9
AC Peak 172.51 1% +/- 1 digit 0.10 0.010 170.68 174.33 172.0
AC Freq 60.00 1% +/- 1 digit 0.10 0.010 59.30 60.70 60
%VD 12 4.40 2.5% +/- 5 digit 0.50 0.025 3.79 5.01 4.4
%VD 15 5.50 2.5% +/- 5 digit 0.50 0.025 4.86 6.13 5.3
%VD 20 7.33 2.5% +/- 5 digit 0.50 0.025 6.64 8.01 7.2
N-G Voltage 0.50 2.5% +/- 5digit 0.50 0.025 -0.01 1.01 0.5
Hot 0.34 5% +/- 5 0.05 0.050 0.27 0.40 0.32
N 0.11 5% +/- 5 0.05 0.050 0.06 0.17 0.13
Gd 0.20 5% +/- 5 0.05 0.050 0.14 0.26 0.22
The GFCI / Time test cannot be done in the field
High Resistance Ground Fault Test (GFCI)
A ground fault circuit-interrupter, the device should be capable of interrupting the
electrical circuit when there is a fault between 6mA and 264 mA with in the time interval
of T in the following relationship