Full Product Manual
Document: September1, 2009 Page 4of 10
Measured Voltage Drop Method
Before we get into the standardization method of a branch circuit it would be good to go
over the difference of Voltage drop {VD} verses % of Voltage Drop {%VD}. In a branch
circuit there is a Current* Resistance {IR} voltage drop across the wire. This is due to the
resistance of each conductor as a function of wire size, length, and device connections.
For most branch circuits the resistance or impedance stays constant while the current
varies. The higher the current the greater the voltage drops. As an example to perform a
voltage drop test and check the % of voltage drop you would need to perform the
following test in the field.
Test equipment needed:
• True RMS Digital multimeter with ACV accuracy of 0.25% and ACC measurement
accuracy of 0.5% or better
• 8 to 12 Ampere, 1500W load with accuracy of .25% or better
Measurements:
• Measure the Branch circuit voltage at no load
• Measure the Branch circuit voltage and current under load
o The current measurement is very critical use the best method possible
o The VD and %VD below would be for the load current measurement.
Calculate Voltage drop for any load we would use the following
Vd= rZ * A
%Vd=(Vd/V)*100
For the following example the no load Voltage is 120V, loaded Voltage 115 with an 8
amp load.
V = Voltage no-load
L
V = Voltage with load
VD = Voltage no-load - Voltage w-Load
I = Load Current
rZ = Total circuit Impedance
Total circuit Impedance is:
• rZ =(V(no-load)-
L
V (w-load))/I
• rZ =(120-115)/8
• rZ =5/8
• rZ =.625