Instructions / Assembly

4
3
Neon Bulb
100-600V AC/DC
LEDs (61-076)
5-600V AC/DC
Continuity
Indicator
120-600V AC/DC
Features:
• VibrationModewithindicatormovement
• Auto-SwitchingVoltage/Continuity
Technology(61-076,61-080)
• Independentsolenoidandelectroniccircuitry
design provides back-up voltage indication
for added safety
• LowImpedance
• ReplaceableTestLeads
• Shieldedprobetips
• Ultrasonicallyweldedando-ringsealedfor
added durability
• Indicates:
•100-600VAC/DC(61-065,61-067)
• 5-600VAC/DC(61-076,61-080)
To Measure AC/DC Voltage:
• Ensurethattheplugforthetestleadsisfully
seatedintothebananajacks.
• Connectthetesterinparallelwiththeloador
circuit.
• Thetesterindicatesthevoltagetype,DC
polarity, and the voltage level.
Warning
Donotexceeddutycyclespecifiedontester.
To Test for Continuity (61-080,61-076):
• Ensurethattheplugforthetestleadsisfully
seatedintothebananajacks.
• Testforcontinuitybyconnectingthetesterto
the de-energized circuit.
• Ifcircuithas<500kΩ,theContinuityLED
lights.
• Reversingprodsonthecircuitundertest
verifiescontinuityversuslowvoltage+DC.
Applications:
• LocatingBlownFuses
With power off (61-076,
61-080):Placetesteracross
the suspected fuse to
perform continuity check.
IfcontinuityLEDlights,the
fuseisgood.Ifnot,the
fuse is defective.
Withpoweron:Placetesteracrossthe
“source”sideofonefuseandtheloadside
ofanadjoiningfuse.Ifnoorlowvoltageis
indicated, the fuse next to the load side prod is
blown.Iflinevoltageisindicated,thefuse
nexttotheloadsideprodisOK.Repeatthe
same test with the prods on the opposite side
of the same two fuses to check the other fuse.