Instruction Manual

www.idealind.com
Installation Instructions - SpliceLine Wire Connectors
Model 42
Do not exceed the rating of these connectors.
Turn OFF power before removing or installing connectors.
Wiring must comply with all applicable electrical regulations.
COPPER TO COPPER ONLY. Do not use on aluminium wire.
Incorrect use of these connectors can cause electrical fires, personal injury or death.
These connectors are suitable for solid and semi-rigid (<7 strands) conductors.
They are not suitable or rated for use with flexible cable with >7 strands.
Strip wires back 13mm.
Grip wire firmly and push conductor into open port.
Use only one conductor per port.
Connectors are reusable on solid wires of the same wire gauge or larger. If reusing
connectors, cut and re-strip conductors
In order to remove a wire, pull and twist the wire back and forth.
DO NOT RE-USE connector on stranded wire.
Model Colour Rating Wire Range
42 Orange 32A / 450V /105°C
Solid: 0.5mm
2
- 4.0mm
2
Stranded*: 1.0mm
2
- 2.5mm
2
*
Stranded wire is limited to ≤ 7 strands
Insertion
Removal RemovalStrip Length
13mm
Test
1/5