Safety in the Field
Thepowerdemandsoftoday’shigh-techworldhavecausedamarkedincreasein
occurrencesandlevelsoftransientovervoltages.TheInternationalElectrotechnical
Commission(IEC)hasdevelopedasafetystandardsmodelformeasurement,controland
laboratoryuse.
Category I–Thesignallevelfortelecommunications,electronicandotherlow-energy
equipmentwithtransient-limitingprotection.Peakimpulsetransientrangeis600–4,000volts
witha30ohmsource.
Category II –Thelocallevelforfixedandnon-fixedpowereddevicesincludingappliances,
lightingandportableequipment.Outletslocatedmorethan30feetfromCATIIIsourcesand
60feetfromCATIVsources.Peakimpulsetransientrangeisfrom600–6,000voltswitha12
ohmsource.
Category III –Thedistributionlevelforfixedprimaryfeedersorbranchcircuits.Circuits
thatareseparatedfromCATIVsourcesbyatleastoneleveloftransformerisolation.Peak
impulsetransientrangeis600–8,000voltswitha2ohmsource.
Category IV (proposed)–Theprimarysupplylevelforthehighestlevelsoftransient
overvoltage.Includestheutilityservicebothoutsideandattheserviceentrance,servicedrop
fromthepoletothebuilding,overheadlinetoremotebuildings,andundergroundlinetoa
wellpump.Peakimpulsetransientrangeis600–12,000voltswithlessthana1ohmsource.
CAT I
Copiers
Electronic
equipment
Low energy
equipment with
transient limiting
protection
CAT II
Appliances,
PCs, TVs
Outlets and long
branch equipment
All outlets at more
than 10m (30 ft)
from Category III
source
All outlets at more
than 20m (60 ft)
from Category IV
source
CAT III
MC Panels
Feeders and short
branch circuits
Distribution
panel devices
Heavy appliance
outlets with “short”
connections to
service entrance
CAT IV
Exterior
Tr ansformers,
Meters
Outside and
service entrance
Service drop from
pole to building
Overhead line to
detached building
Underground line
to well pump
Service
Entrance
Service
Entrance
Meter
Meter
Meter
Transformer
Outbuilding
Underground Service
Service
Entrance
Outbuilding
Underground Service
METER REPACEMENT PARTS
SELECTION GUIDE
090 310 340 360 480 490 600 610 700 740 760 770 790
61-096
61-310
61-312
61-340
61-342
61-361
61-484
61-486
61-497
61-498
61-605
61-610
61-614
61-702
61-704
61-744
61-746
61-763
61-765
61-773
61-775
61-795
61-797
FUSES
F-1 0.5A (250V) 6.35 x 38mm
F-105 1A (600V) 10.3 x 35mm
F-310 250mA (250V) 5 x 20mm
F-312 500mA (250V) 5 x 20mm
F-314 10A (250V) 5 x 20mm
F-340 0.5A (500V) 6.35 x 32mm
F-341 10A (1000V) 10 x 38mm
F-497 440mA (1000V) 10 x 35mm
F-498 11A (1000V) 10 x 38mm
F-797 315mA (1000V) 5 x 32mm
LA-3893 2A (600V) 6.35 x 25.4mm
LA-3898 0.25A (500V) 5 x 32mm
BATTERIES
61-201 1.5V (LR44)
1.5V (AA)
1.5V (AAA)
9V
TEST LEADS
TL-34 Leads w/pin connectors
TL-56 Test leads
TL-95 Test leads
TL-100 Test leads w/alligator clips
TL-102 Silicone test leads
TL-104 Test leads w/large alligator clips
TL-310 Test leads
TL-795 Test leads
TL-797 Test leads
Safety in the Field
Visit our website for more technical product details,
application support, white papers, videos and software!