Cut Sheet

B-76
WWW.iDeALinDustries.Com 1-800-435-0705 Customer AssistAnCe
Tools & supplies
HeaT sHrinKable Tubing
Thermo-Shrink
®
Thin-Wall
Heat Shrinkable Tubing
Polyolefin material electrically insulates and protects
in-line components, disconnect terminals and splices
with its high strength and excellent resilience
Use to bundle wires for very flexible light-duty
harnesses
Highly flame-retardant and flexible; resistant to
common fluids and solvents
Meets UL 486D 125°C VW-1 600V; Material:
NoPBB’s,PBBE’s,conformstoROHS
2:1 shrink ratio; Minimum shrink temperature: 70°C;
Operatingtemperature:-55°Cto+125°C
• RoHScompliant
Normal
Size (in.)
Expanded
I.D. (Min.)
Nominal
Recovered
I.D. (Max.)
Recovered
Wall
Thickness
+/- 10%
Cable
Range
AWG*
Length
(Pkg.)
Cat. No.
3/64 0.063”/1.6mm 0.024”/0.6mm 0.013”/0.33mm 22-18 4 ft. (Disk) 46-600
1/16 0.079”/2.0mm 0.031”/0.8mm 0.014”/0.36mm 16 4 ft. (Disk) 46-601
3/32 0.122”/3.1mm 0.047”/1.2mm 0.017”/0.44mm 14-12 4 ft. (Disk) 46-602
1/8 0.146”/3.7mm 0.063”/1.6mm 0.017”/0.44mm 24-20
6 in. (Bag) 46-310
4 ft. (Disk) 46-603
1,000 ft.
(Spool)
46-312
3/16 0.205”/5.2mm 0.094”/2.4mm 0.020”/0.50mm 20-14
6 in. (Bag) 46-313
4 ft. (Disk) 46-604
1,000 ft.
(Spool)
46-315
1/4 0.268”/6.8mm 0.126”/3.2mm 0.022”/0.56mm 14-8
6 in. (Bag) 46-316
4 ft. (Disk) 46-605
500 ft.
(Spool)
46-318
5/16 0.346”/8.8mm 0.157”/4.0mm 0.022”/0.56mm 10-6 4 ft. (Disk) 46-606
3/8 0.421”/10.7mm 0.185”/4.7mm 0.022”/0.56mm 8-4
6 in. (Bag) 46-319
4 ft. (Disk) 46-607
200 ft.
(Spool)
46-321
1/2 0.539”/13.7mm 0.252”/6.4mm 0.026”/0.65mm 4-1
6 in. (Bag) 46-322
4 ft. (Disk) 46-608
200 ft.
(Spool)
46-324
3/4 0.807”/20.5mm 0.374”/9.5mm 0.027”/0.69mm
2-250
MCM
6 in. (Bag) 46-325
4 ft. (Disk) 46-609
200 ft.
(Spool)
46-327
1 1.043”/26.5mm 0.500”/12.7mm 0.031”/0.80mm
2/0-500
MCM
6 in. (Bag) 46-328
4 ft. (Disk) 46-610
100 ft.
(Spool)
46-330
*Reference only - Consult the wire manufacturer’s catalog for specific O.D. of wire and insulation.
Technical Data
Property Test Method Typical Data
Tensile strength ASTM D 638 14MPa
Elongation at break ASTM D 638 600%
Elongation after aging at 175°C for 168 hours UL 224 350%
Flammability UL 224 VW-1 Pass
Heat shock (250°C/4 hours) UL 224 No cracking
Cold bend test (-55°C/4 hours) UL 224 No cracking
Dielectric strength ASTM D 150 20KV/mm
Volume resistance ASTM D 876 1014Ω.cm
Copper corrosion UL 224 Pass
Chemical resistance UL 224 Pass
Longitudinal shrinkage UL 224 0±5%
Eccentricity UL 224 30%
Thermo-Shrink
®
Medium-Wall Heat Shrinkable End Caps
Technical Data
Property Test Method Typical Data
Operating Temperature IEC 216 -55°CC to +110°C
Tensile Strength ASTM D 638 >14 MPa
Elongation at break ASTM D 638 >400%
Density ASTM D 792 1.05g/cm3
Elongation of break after aging 150°C, 168 hrs. >300%
Dielectric Strength IEC 243 >15KV/mm
Volume Resistance IEC 93 1014Ω.cm
Expanded
I.D. (Min.)
Recovered
I.D. (Max.)
Recovered
Wall Thickness
+/-10%
Cable Dia. Range* Length Cat. No.
0.55”/14mm 0.18”/4.5mm 0.079”/2.0mm 0.20”/5mm - 0.47”/12mm 1.77”/ 45mm
46-381
0.98”/25mm 0.31”/8mm 0.091”/2.3mm 0.39”/10mm - 0.71”/18mm 2.76”/ 70mm
46-382
1.38”/35mm 0.59”/15mm 0.118”/3.0mm 0.67”/17mm - 1.18”/30mm 3.35”/ 85mm
46-383
2.95”/75mm 1.38”/35mm 0.138”/3.5mm 1.77”/45mm - 2.76”/70mm 5.12”/ 130mm
46-384
*Consult the wire manufacturer’s catalog for specific O.D. of wire and insulation.
Creates a watertight seal
to protect ends of power
and control cords
Protects against oxidation,
ozone, UV radiation, etc.
•
Coated with hot melt
adhesive to ensure
environment seal
•
Fits easily over end
of cable
•
Protect power cables
up to 1000V and
telecommunication
cable
•
Recommended for both open air and
underground power distribution cables with
PVC, lead or XLPE sheaths
Thermally stabilized cross-linked polylelin,
coated with specially designed hot melt
adhesive
CU
S