Instruction Manual

www.idealind.com
Installation Instructions - Push-In Wire Connectors
Models 32, 33, 34, 87, 88 & 90
Do not exceed the rating of these connectors.
Turn OFF power before removing or installing connectors.
Wiring must comply with all applicable electrical regulations.
COPPER TO COPPER ONLY. Do not use on aluminium wire.
Incorrect use of these connectors can cause electrical fires, personal injury or death.
These connectors are suitable for solid and semi-rigid (<7 strands) conductors.
They are not suitable or rated for use with flexible cable with >7 strands.
Strip wires back 13mm.
Grip wire firmly and push conductor into open port.
Use only one conductor per port.
Connectors are reusable on solid wires of the same wire gauge or larger.
If reusing connectors, cut and re-strip conductors.
In order to remove a wire, pull and twist the wire back and forth.
DO NOT RE-USE connector on stranded wire.
Specifications
Model 32
Red
2-Port
Model 33 Orange
3-Port
Model 34 Yellow
4-Port
Model 87 Grey
5-Port
Model 88 Blue
6-Port
Model 90
Black
8-Port
Rating 32 Amp / 450V /
105°C maximum
24 Amp / 450V /
105°C maximum
Depth 19.81 mm 18.52 mm 18.52 mm 18.21 mm
Width 13.21 mm 17.53 mm 20.83 mm 23.03 mm 15.32 mm 35.03 mm
Height 9.65 mm 9.02 mm 15.42 mm 9.02 mm
Wire
Combination
Range
Solid wire 0.75mm
2
to 4.0mm
2
0.75mm
2
to 4.0mm
2
Stranded wire* 1.5mm
2
to 2.5mm
2
1.5mm
2
to 2.5mm
2
*
Stranded wire is limited to ≤ 7 strand
1/5
13mm
Strip Length Removal RemovalInsertion