SRC2100– 120/277 VAC Single Room Controller
ND xxxx-1 08/2017 Users Manual – SRC2100 Single Room Controller
Page 3
www.idealindustries.com
LOAD
The LOAD(red) and Neutral(White) wire are 18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect Controller LOAD wire to the ballast hot line with appropriate sized wirenut or push-
in connector if necessary.
3. Connect Controller NEUTRAL Output to the ballast neutral with appropriately sized wirenut
or push-in connector if necessary.
4. For feed-through (i.e., “daisy-chain”) installations, connect the LOAD hot feed-through
conductor into the wirenut in step 2. Also, connect the NEUTRAL Output feed-through
conductor into the wirenut in step 3.
DIM Connector
The DIM wires are18 AWG solid copper conductors.
1. Strip wires to 1/2”.
2. Connect positive/(+)/purple DIM wire from Controller to positive/(+)/purple wire from dimming
ballast with appropriate sized wirenut or push-in connector if necessary.
3. Connect negative/(-)/grey DIM wire from Controller to negative/(-)/grey wire from dimming
ballast with appropriate sized wirenut or push-in connector if necessary.