Installation Manual

20
Figure 5-2
5.4
RS485 Bus FAQ
Phenomenon
Possible Reasons
Solution
Speed dome
can run self-
diagnosis but I
cannot control
it.
Host address(baud rate) and
speed dome address(baud rate)
are not match;
Positive and negative end of
RS485 Bus are misconnected;
Connection cable is loose
RS485 Bus connection are cut
off;
Modify host or speed dome setup
Switch RS485 positive end and
negative end
Fix connection cable firmly
Replace RS485 Bus.
I can control
the speed
dome but is not
smooth
RS485 Bus connection are not
good
One RS485 bus is off
The distance between host and
speed dome is too far
Parallel connected too much
speed domes.
Connect RS 485 Bus again
Replace RS485 Bus
Add terminal matching resistance
Add RS485 distributor.