Installation guide
Forhurricanetiedowns- contactyourlocaldistributorfor
detailsandPE(ProfessionalCertification),ifrequiredbylocal
authorities.
Onrooftopapplications,mountonlevelplatformorframe.
Placeunitabovea load-bearingwallandisolateunitand
tubingsetfromstructure.Arrangesupportingmembersto
adequatelysupportunitandminimizetransmissionof
vibrationto building.Consultlocalcodesgoverningrooftop
applications.
Roofmountedunitsexposedto windsmayrequirewind
baffles.ConsulttheLow-Ambientpressureswitchinstallation
instructionsforwindbaffleconstruction.
NOTE:Unitmustbe levelto within+2° (+3/8 in./ft..) per
compressor manufacturer specifications.
Clearance Requirements
When installing, allow sufficient space for airflow clearance,
wiring, refrigerant piping, and service. Allow 30 in. (762 mm)
clearance to service end of unit and 48 in. (1219.2 mm)
above unit. For proper airflow, a 6 in. (152.4 mm) clearance
on one side of unit and 12 in. (304.8 mm) on all remaining
sides must be maintained. Maintain a distance of 24 in.
(609.6 mm) between units. Position so water, snow, or ice
from roof or eaves cannot fall directly on unit.
Figure 2 J Tie Down Knockouts
3/8-in. (9.53 mm) Dia.
Tiedown Knockouts in
Basepan(2) Places
1
View From Top
UNIT BASE PAN
Dimension
31-1/2 X 31-1/2
35 X 35
TIEDOWN KNOCKOUT LOCATIONS in. (mm)
A B C
9-1/8 (231.8) 6-9/16 (166,7) 24-11/16 (627.1)
9-1/8 (231.8) 6-9/16 (166,7) 28-7/16 (722,3)
On rooftop applications, locate unit at least 6 in. (152.4 mm)
above roof surface.
Operating Ambient
The minimum outdoor operating ambient in cooling mode is
55°F (12.78°C) without low ambient cooling enabled, and the
maximum outdoor operating ambient in cooling mode is
125°F (51.67°C).
Make Piping Connections
PERSONAL INJURY AND ENVIRONMENTAL
HAZARD
Failure to follow this warning could result in personal
injury or death.
Relieve pressure and recover all refrigerant before system
repair or final unit disposal.
Use all service ports and open all flow-control devices,
including solenoid valves.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Do not leave system open to atmosphere any longer than
minimum required for installation. POE oil in compressor is
extremely susceptible to moisture absorption. Always keep
ends of tubing sealed during installation.
If ANY refrigerant tubing is buried, provide a 6 in. (152.4
mm) vertical rise at service valve. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without
further special consideration. Do not bury lines more than
36 in. (914.4 mm).
Outdoor units may be connected to indoor section using
accessory tubing package or field-supplied refrigerant grade
tubing of correct size and condition. For tubing requirements
beyond 80 ft/24.38 m, substantial capacity and performance
losses can occur. Following the recommendations in the
Long Line Applications Guideline for Split-System Air
Conditioners and Heat Pumps will reduce these losses. Refer
to Table 1 for accessory requirements. Refer to Table 2 for
field tubing diameters.
There are no buried-line applications greater than 36 in.
(914.4 mm).
If refrigerant tubes or indoor coil are exposed to atmosphere,
they must be evacuated to 500 microns to eliminate
contamination and moisture in the system.
Outdoor Unit Connected to Factory Approved
Indoor Unit
Outdoor unit contains correct system refrigerant charge for
operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field-supplied or
factory-accessory tubing, and factory supplied filter drier.
Check refrigerant charge for maximum efficiency.
Table 1 - Accessory Usage
REQUIRED FOR LOW-AMBIENT
COOLING APPLICATIONS
(Below 55°F / 12,8°C)
Yes
Yes
Yes
No
Yes
Recommended
Yes
Yes
REQUIRED FOR LONG LINE
Accessory APPLICATIONS* (Over 80 ft. / 24.38 m)
Crankcase Heater Yes
Compressor Start Assist Capacitor and Relay Yes
Evaporator Freeze Thermostat No
Liquid Line Solenoid Valve See Long Line Applications Guideline
Low-ambient Pressure Switch No
Support Feet No
Thermal Expansion Valve (TXV) Yes
Hard Shutoff
Winter Start Control No
For tubing line sets between 80 and 200 ft, (24.38 and 60,96 m) and/or 20 ft, (6.09 m) vertical differential, refer to Long Line Applications Guideline.
421 01 5104 03 Specifications subject to change without notice. 3