I Split System Condensers
Figure Sensor Probe Mounting
(1) Pull ambient sensor probe through 3/8" diameter hole located on
the external electrical connection panel.
318" D]a'. Hole _Q I
Sensor Probe
(2) Locate the plastic snap bushing 1/8" to 114"from sensor probe and
clamp sensor probe leads.
1/8"TO 1/4"
_/ Bushing
Sensor Probe
(3) Push the plastic bushing into the 3/8" diameter hole and snap it into
place.
Figure !i
Installation Instructions
A/C Condenser Typical Low
Voltage Connections
(Compressor
Indoor
Thermostat
(Co
Outdoor
Unit
ontactor)
Y--
nmon 24V)
=--Y-
Sensor Probe Sensor Probe
(front view) (side view)
R G BL W
! I I !
INDOOR GAS
BLOWER OR FURNACE
COIL
Figure i2 Heat Pump Typical Low Voltage Control Connections
--@
White Rogers 1F92 only,
field jumper required
Y1-Wl.
Indoor
Thermostat
C
NOTE: White Rogers 1F92
thermostat cannot be used
for direct staging of electric
heat, Outdoor thermostat
must be used for staging.
ELECTRIC HEAT
NO OUTDOOR THERMOSTAT
\
\__
I
INDOOR ACCESSORY
BLOWER ELECTRIC
COIL HEAT PKG.
I
Outdoor
Unit
-0-- O -- (Heat/Cool Relay)
-0-- Y- (Compressor)
-Q-- W-- (Electric Heat)
-0-- BL-- (Common 24V)
-O-- R D (24V-Hot)
SPLICE (WIRE NUT OR SOLDER AND TAPE)
(1) FIRST STAGE ELECTRIC HEAT ALL HEATERS
(2) ADDITIONAL STAGES, ELECTRIC HEAT STAGE 2 = BK,
STAGE 3 = V, STAGE 4 = BR
If electric heat is not used, discard connection shown from electric heat package.