Installation guide

6,Routeunitpowersupplythroughknockoutintopof
unitandconnecttolinesideofdisconnect.Connect
groundwiretogroundlug.Seewiringlabeltomake
connections.
Figure 1 Cooling Control Kit
A98333
NOTE: Toppanel not shown for clarity
COOLING J j
CONTROL
.-/
BLOWER
ACCESS UNIT
DOOR
A98335
7. Remove disconnect pullout,
8. Replace access panel.
9, Insert disconnect pullout through hole in access
panel,
Figure 2 Heater Package
HEATER
PACKAGE
A98332
NOTE: Top panel not shown for clarity
ACCESS
DOOR
INDOOR
UNIT
A98334
Figure 3 J Electrical Data
NOM HEATER WIRE
PART UNIT HEATER MIN WIRE MIN MAX CIRCUIT
CAPACITY RATING
NO. SIZE VOLTAGE KW @ AMPS SIZE* AMPACITY PROTECTION
240-V (BTUH) (°c)
018
AMWK001CK 024 208/230 0 0.0/0.0 0/0 75 14 2,5 15/15
O3O
018
AMWK005AH 024 208/230 5.0 18.1/20.0 12799/15700 75 10/10 25.2/27.5 30/30
O3O
018
AMWK007AH 024 208/230 7.5 27.1/30.0 19215/23515 75 8/8 38.4/40.0 40/40
O3O
018
AMWK011AH 024 208/230 11.0 39.8/44.0 25597/31331 75 6/6 52.3/57.5 60/60
030
664 01 3004 00 2L_ J