Installation guide

I Fan Coils
No Heat Kit Installation
(FCP --C and FCX)
If electric heat is not used, install accessory No Heat Kit.
1. Locate adapter and filler plates, with screws inside pack-
age.
2. Attach adapter plate and filler plate to bracket if required to
match cabinet, Refer to Figure 10.
3. Secure the electric heat accessory with four screws.
4. Connect the plug from No Heat Kit wiring into the recep-
tacle on the control board on the side of the cabinet.
CAUTION
Do not attempt to force plug as it only fits one way.
Grounding Connection
Use a copper conductor(s) from the Green ground wire on the unit
or ground lugs on the electric heater to a grounded connection in
the electric service panel or a properly installed grounding rod.
Figure !i Typical Low Voltage Schematic
Heat Pump with Electric Heat
Installation Instructions
Typ,ca,LowVo,tage
Schematic
1
Cooling Only
Thermostat
R
G --
Y
W
000 00() () 1
W 1 W2 G Y H O C R
Indoor Blower
Staging
_ermostat
R I
--i
G I
c I
---------t
o I
y I
=========4
w2 I
W 1 I--
W t W2 G Y H O C
IndoorBlower
Outdoor Unit
R
BL
W
-- y
O
Cooling with Electric Heat
Outdoor Unit
Y
Y
Outdoor Unit
Therrnoctat
R
W --
o wo O
R
Electrical Data
Maximum
Overcurrent
Supply Maximum Branch Protective
SupplyCircuit Circuit Motor Total Circuit Device
Volts Phase Hertz No. AMPS. AMPS. Ampacity (AMPS.)
240 1 80 Single 60 60 75 15
208 1 60 Single 60 60 75 15
Nomi- Supply Heater Mexi- Branch
Heater Supply Heating Heat- KW Per Circuit KW Per Heater Motor Total Circuit
Voltage BTUH KW Element No. Circuit AMPS. AMPS. AMP Ampacity
1086081 240 16,832 4.8 4.8 Single 48 200 60 26.0 325
05KW 208 12,287 3.6 3.6 Single 36 173 60 23.3 292
1086082 240 24573 7.2 3.6 Single 72 300 60 36.0 450
07KW 208 18430 5.4 2.7 Single 54 260 60 32.0 400
1086083 240 32,765 9.6 4.8 Single 96 400 60 46.0 575
10KW 208 24,574 7.2 3.6 Single 72 347 60 40.7 508
Recommended
SupplyWire
750C. Copper Ground
Max. Wire
He. Size Length (Ft) No. Size
2 14 104 1 14
2 14 g0 1 14
Me,mum Recommended
Overcurrent Supply Wire
Protective 750 C. Copper Ground
Device Max. Wire
(AMPS.) No. Size Length (F No. Size
35 2 10 61 1 10
30 2 10 59 1 10
45 2 8 70 1 10
40 2 8 68 1 10
60 2 6 85 1 10
60 2 6 83 1 10