These instructions must be read and understood completely before attempting installation. Safety Labeling and Signal Words DANGER, WARNING, The _ signal CAUTION, and NOTE _ words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and th hout thi apply to the product.
Required Notice for Massachusetts Installations Important The Commonwealth of Massachusetts requires compliance with regulation 248 CMR 5.08: Modifications to NFPA-54, as follows: Chapter 10 2) Revise 10.8.
Safety Considerations changing residential construction practices. We instructions as a minimum for a safe installation. Follow FIRE, EXPLOSION, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING HAZARD AND Failure to follow this warning could result in dangerous operation, personal injury, death, or property damage.
to combustible construction. Maintain a 1-in. (25 mm) clearance from combustible materials to supply air ductwork for a distance of 36-in. (914 mm) horizontally from the furnace. See NFPA 90B or local code for further requirements. Table 1 Freeze Figure 1 SUPPLY AIR Minimum Clearances to Combustible Materials for All Units CLEARANCE In(mm) REAR FRONT (Combustion air openings in 0 1 (25) and Return Air MAX 80°F/27°C ». ¢ POSITION Protection Temperature ?.2. 12.
1. Combustion and Ventilation Air e US: Section 9.3 of the NFPA54/ANSI Air for Combustion and Ventilation ¢ CANADA: Part 8 of the CAN/CSA B149.1-2010, Venting Systems and Air Supply for Appliances Disconnect all power to the furnace. Multiple disconnects may be required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND. Z2223.1-2009, 2.
Figure 2 | Dimensions | BS NOTES: 1. Doors may vary by model. [ies O 2. Minimum b | $ OY \Y 5 p rorview al gaye [70.45 return-air openings at furnace, based on metal duct. If flex duct is used, see flex duct manufacturer's recommendations for equivalent diameters. a. For 800 CFM-16-in. (406 mm) round or 14 1/2 x 12-in. (368 x 305 mm) rectangle. b. For 1200 CFM-20-in. (608 mm) round or 14 1/2 x 19 1/2-in. (868 x 495 mm) rectangle. ce. For 1600 CFM-22-in. (659 mm) round or 14 1/2 x 22 1/16-in.
Locat ion 4. CAUTION e be located close to the chimney or vent and attached to an e air distribution system. Refer to Air Ducts section. be provided ample space for servicing and cleaning. Always comply with minimum fire protection clearances shown PERSONAL HAZARD Improper use or installation of this furnace may result in premature furnace component failure.
Figure 3 Multipoise Orientations AIRFLOW L\ THE BLOWER IS LOCATED TO THE RIGHT OF THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED TO THE LEFT. THE BLOWER IS LOCATED BELOW THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED UPWARD. UPFLOW AIRFLOW AIRFLOW DOWNFLOW THE BLOWER IS LOCATED ABOVE THE BURNER SECTION, AND CONDITIONED AIR IS DISCHARGED DOWNWARD.
Air for Combustion Ventilation and CARBON Introduction When the furnace is installed as a direct vent (2-pipe) furnace, no special provisions for air for combustion are required. However, other gas appliances installed in the space with the furnace may require outside air for combustion. Follow the guidelines below to insure that other gas appliances have sufficient air for combustion.
Indoor Combustion Air? NFPA & AGA Standard Methods and Known-Air-Infiltration and 2. Determine Rate minimum required volume for each total minimum required volume for the space. Table 4 Indoor combustion air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Rate Method is used. - Minimum Space Volumes were determined by using the following equations from the National Fuel Gas Code ANSI 2223.1/NFPA 54-2009, 9.3.2.2: 1.
Combination Air for Combustion, Ventilation, and Dilution from Indoors Figure 7 Indoor 1. of Indoor and Outdoor Air openings shall comply with the Indoor Combustion Air Method below and, CIRCULATING AIR DUCTS Outdoor openings 2. VENT shall be located as required in the Outdoor Combustion Air Method mentioned previously and, Outdoor openings shall be sized as follows: . Calculate the Ratio of all Indoor Space volume a divided by required volume for Indoor Combustion eq FZ =TSQin.
Table 4 | Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors OTHER THAN FAN-ASSISTED TOTAL (1,000°S BTUH GAS INPUT RATE) 30 ACH 0.60 [| 1,050 40 | FAN-ASSISTED TOTAL (1,000°S BTUH GAS INPUT RATE) 50 40 {| 60 | Space Volume Ft? 3 (M*) 80 | 100 | 120 | 140 ; (29.7) (39.6) 1,400 1,750 (49.5) (39.6) (42.5) 1,500 2,000 2,500 3,000 3,500 0.50 1,260 (35.6) 1,680 (47.5) 2,100 (59.4) 1,680 (47.5) 1,800 (51.
Figure 9 Unconverted Factory Configuration as viewed Remove 4 { Remove . . relief tube from relief in the Downflow Orientation pressure switch tube from front pressure switch and discard. A new tube is shipped in the loose parts bag. g ; Remove tube from relief port. 3 port on condensate trap. © ia ae oo ‘S . | J Remove the screw that secures the trap to the collector box and v — ° ° = o Os | L remove trap.
Condensate Trap - Horizontal Orientation When the furnace is installed in the horizontal right position, the condensate trap will be initially located at the bottom of the collector box, as received from the factory. See the top image in Figure 10. When the furnace is installed in the horizontal left position, the condensate trap will be initially located at the top of the collector box, as received from the factory. See the top image in Figure 11.
Horizontal Right Trap Configuration (CONTINUED) NOTE: Remove knockout in casing before re-installing the condensate trap. Slide relief tube in stand-offs to adjust length. SOE ee y fH v1 Vent elbow shown in alternate Attach condensate (1) trap with screw to orientation. collector box. inlet to vent elbow 15 I|b.-in. Install plug on open port of collector box Tighten clamp on Align trap over middle and right-hand port on collector box.
Horizontal Left Trap Configuration (CONTINUED) NOTE: Remove knockout in casing before re-installing the condensate trap. Rotate elbow to desired position and torque clamp on inlet 15 lb.-in. { Install two plugs previously removed in open ports on collector box. 4 Connect relief tube to port on collector box. ° ] ° ‘ 6 Slide relief tube in stand-offs to adjust length. Ze 7) Attach condensate trap with screw to collector box.
7. Install the adapter or connect the 4/2-in. CPVC pipe by sliding a spring clamp over the open end of the grommet on the outside of the furnace casing. 8. Open the spring clamp and insert the long end of the adapter of the 1/2-in. CPVC pipe into the outlet stub on the drain elbow. 9. Connect additional condensate piping to a code-approved drain, or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral and vegetable oils, such as canola oil.
8. Remove the knock-out for the condensate trap in the side of the casing. 4. Install the drain trap grommet in the casing, if required for direct-vent applications. If necessary, remove the trap, install the grommet and re-install the trap. 5. Remove the pre-formed rubber drain spring clamps from the loose parts bag. elbow and Figure 14 Modify Rubber Drain Elbow Cut line for left side condensate drain. Do not discard parts after cutting. two 6.
Figure 16 Formed Rubber Drain Grommet / PULL DRAIN STUB THROUGH CASING, | Furnace Pitch Requirements LEVEL 0-IN. (0 MM) TO 4/2-IN. (13 MM) MAX INSTALL CLAMPS ON DRAIN ELBOW ATTACH DRAIN ELBOW TO CONDENSATE,__ DRAIN TRAP Figure 18 | / f Se MIN 1/4-IN. (6 MM) TO 1/2-IN. (13 MM) MAX : | FRONT UPFLOW OR DOWNFLOW HORIZONTAL A11237 Supply Air Connections For a furnace not equipped with a cooling coil, the outlet duct shall be provided with a removable access panel.
Figure 19 | Removing Bottom Closure Panel 8. Install another nut on other side of furnace base. (Install flat washer if desired.) 4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement. Reinstall bottom closure panel if removed. DOWNFLOW INSTALLATION NOTE: The furnace must be pitched as shown in Figure 18 for proper condensate drainage.
4. subbase, or a factory-approved air conditioning coil casing. DO NOT cut main furnace casing to attach supply air duct, humidifier, or other accessories. All supply-side accessories MUST FIRE, EXPLOSION, AND POISONING HAZARD be connected to duct external to furnace casing. Return Air Connections A failure to follow this warning could injury, death and/or property damage. Never connect return-air ducts furnace. Follow instructions below. to cause the personal back of 4.
Table 5 Opening Dimensions - in. (mm) FURNACE CASING WIDTH IN.
Figure 25 | Suspended Furnace Installation COMBUSTION -.AIR PIPE (SEE VENTING SECTION) 1/4-IN ROD g NOTE: & cys a oN EXTEND = hee << Mt = ANGLE IRON OUT FOR COIL SUPPORT NOTES: 1.A 7 In. (25mm) clearance minimum between HEX NUT & WASHER (4) REQD. PER ROD ROD LOCATION USING DIMPLE LOCATORS top of furnace and combustible material 2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage. 3.
Roll-Out Protection Provide a minimum 12-in. x 22-in. (305 x 559 mm) piece of sheet metal for flame roll-out protection in front of burner area for furnaces closer than 12-in. (805 mm) above the combustible deck or suspended furnaces closer than 12-in. (805mm) to joists. The sheet metal MUST extend underneath side and bottom of the furnace.
Table 7 | Filter Media Pressure Drop (Clean) Versus Airflow - in. w.c. (Pa) Factory-Accy 14x 25 Filter Representative After-Market Filter Media* Washable CFM L/s 600 800 1000 1200 (283) (378) (472) (566) (1-in. /2.5 cm) 0.04 0.06 0.07 0.08 (12) (15) (18) (20) Fiberglass* (1-in. /2.5 cm) 0.07 0.10 0.13 0.17 (17) (25) (34) (43) Factory-Accy 16x 25 Filter L/s 600 800 1000 1200 1400 1600 1800 (283) (378) (472) (566) (661) (755) (850) (1-in. /2.5 cm) 0.04 0.05 0.06 0.07 0.08 0.09 0.
Downflow Return Air Configurations and Restrictions Figure 27 External Filter Cabinet Configurations Figure 30 | Accessory Bottom Filter Rack | @ RETURN / > AIR SIDE RETURN . NOT PERMITTED FOR ANY MODEL © ® RETURN AIR ® ® SIDE RETURN NOT PERMITTED FOR ANY MODEL Q @ Y f \ L1OFO33 Fiqure 28 g Upflow Return Air Configurations and Restrictions —_— SUPPLY | AIR : L1OF031 B A eS ° ® £ ® # /O) q ° ® RETURN < © Oo A RETURN AIR. AIR 22-5/16 | (666.
Figure 31 Systems Design Guidelines reference tables available from your local distributor. The duct system should be sized to handle the required system design CFM at the design external static pressure. The furnace airflow rates are provided in the | Accessory Side Filter Rack Service a and Technical Support Manual.
Table 10 | Maximum FIRE OR EXPLOSION Capacity of Pipe RON PIPE INTERN AL LENGTH OF PIPE - FT (M) IN.Size(MIM) IN. (MM) 6 0) é 0) a") 1/2 (13) 0.622 (158) 175 120 97 3/4 (19) 0.824 (20.9) 360 250 200 170 151 1.049 (26.6) | 680 465 375 320 285 HAZARD Failure to follow this warning could result in personal injury, death, and/or property damage.
Figure 33 | Gas Valves Figure 34 Redundant Automatic Gas Valve (Two-Stage) Gas Entry Left Side Gas Entry. Gas Pipe Grommet Required For Direct Vent Applications.
4. 115-V Wiring Furnace must have and grounded. a 115-v power supply properly connected WARNING FIRE HAZARD Failure to follow this warning could result in personal injury, death, or property damage. Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire. NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control status indicator light flashes rapidly and furnace does NOT operate.
Heating and Cooling Application Two-Stage Wiring Diagram with Single-Stage Thermostat --- > FIELD 24-VOLT WIRING === = FIELD 115-, 208/230-, 460-VOLT WIRING awn FACTORY 24-VOLT WIRING a——— 1-STAGE THERMOSTAT FIVE WIRE BLOWER DOOR ONLY t Keel [pot PM worl, ow wari Qw C w) 0] Gf N an 4 = SUPPLIED DISCONNECT ' t t t u u i a t a 1 ro pe 1 q O & t FUSED DISCONNECT 208/230- OR =\460-VOLT PHASE enn t ~--d mm JUNCTION BOX ' m= of om wollen om to 115-VOLT FIELD-| FIELD-SUPPL
Figure 37 J-BOX _. MOUNTING\, SCREWS | J-Box Bracket Installation Field-Supplied Electrical Box on Furnace Casing Figure 38 _ J-BOX MOUNTING ~~ BRACKET GROUND NEUTRAL LINE VOLTAGE GROUND SCREW J-BOX COVER L12F025 Remove the J-Box cover and mounting bracket from the loose parts bag. Select a 7/8-in. (22 mm) knock-out on the desired side of the casing. Remove the knock-out from the casing. Drill two 1/8-in. (8 mm) pilot holes in the casing dimples by the desired 7/8-in. (22 mm) knock-out.
NOTE: Use AWG No. 18 color-coded copper thermostat wire for lengths up to 100 ft. (80.5 M). For wire lengths over 100 ft., energized when 24 VAC the Induced HUM terminal Draft Relay closes. is energized when The the low use AWG No. 16 wire. The 24-v circuit contains an automotive-type, 3-amp. fuse located on the control. Any direct shorts during installation, an service, a 24 VAC humidifier to the 24 VAC HUM terminal and or maintenance could cause this fuse to blow.
Table 11 Electrical Data (F/G)9MVT TWO-STAGE, VARIABLE SPEED FURNACES VOLTSHERTZUNIT SIZE | PHASE 0401410 | 115-60-1 0601714 | 115-60-1 0801716 | 115-60-1 0802120 | 115-60-1 1002120 | 115-60-1 1202422 | 115-60-1 VOLTSHERTZUNIT SIZE | PHASE 0401410 | 115-60-1 0601714 | 115-60-1 0801716 | 115-60-1 0802120 | 115-60-1 1002120 | 115-60-1 1202422 | 115-60-1 VOLTSHERTZUNIT SIZE | PHASE 0401410 | 115-60-1 0606014 | 115-60-1 0801716 | 115-60-1 0802120 | 115-60-1 1002120 | 115-60-1 1202422 | 115-60-1 FotAGE: MI
Figure 40 Example of Variable Speed Furnace Control for ECM Blower Motor - (F/G)9MVT COMMUNICATION CONNECTOR MODEL PLUG CONNECTOR CONTINUOUS FAN OUTDOOR (CF) AIRFLOW AIR TEMP SETUP SWITCHES | CONNECTOR sW4 SETUP SWITCHES SW1 SETUP SWITCHES AND BLOWER OFFDELAY _s AIR CONDITIONING (NO) AIRFLOW SETUP SWITCHES s x g HUM = o = ACRDS § 24-V THERMOSTAT TERMINALS a O a FLASH UPGRADE CONNECTOR (FACTORY ONLY) a ————-—"P.
Example of Single Stage Furnace Control for ECM Blower Motor - (F/G)9MXE Figure 42 HEAT OFF-DELAY 24-V THERMOSTAT TERMINALS < TWINNING AND/OR COMPONENT TEST TERMINAL HUMIDIFIER TERMINAL (24-VAC 0.
Lapprét GVS-65 (Purple \ et le ciment-solvant GVS8-65 doivent étre utilisé avec les Royal Pipe. Systeme IPEX 636, apprét PVC/CPVC, Purple pour évacuation des gaz de combustion et systeéme IPEX 636(1)t, ciment PVC pour évacuation des gaz de combustion, cote classe IIA, 65 deg C. doivent étre utilisés avec le systeme d’évacuation IPEX 636 — Ne pas combiner | ‘apprét et le ciment d’un manufacturier avec un systeme d’évacuation d’un manufacturier différent.
Venting Systems 4. CARBON NOTICE WARNING MONOXIDE POISONING OPTIONAL CONFIGURATION AIR INLET PIPE HAZARD Failure to follow the instructions outlined in Locating the Vent Termination for each appliance being placed into operation could result in carbon monoxide poisoning or death. For all venting configurations for this appliance and other gas appliances placed into operation for the structure, provisions for adequate combustion, ventilation, and dilution air must be provided in accordance with: U.S.
4. CARBON WARNING MONOXIDE POISONING HAZARD Failure to follow the instructions outlined in Locating the Vent Termination for each appliance being placed into operation could result in carbon monoxide poisoning or death. The instructions included with this furnace DO NOT APPLY to vent systems that are located below the fur- nace.
Figure 43 Vent Coupling and Adapter with Gaskets Locating the Vent Termination General NOTE: Termination Requirements for the Provinces of Alberta and Saskatchewan are located at the end of this section. Combustion-air inlet pipe (Direct Vent/2-Pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof.
or tee, certified to ULC S636 must be used. CARBON MONOXIDE POISONING The concentric vent kit currently cannot be modified to attach HAZARD Failure to follow the instructions outlined in Locating the Vent Termination for each appliance being placed into operation could result in carbon monoxide poisoning or death.
Figure 48 Vent Terminations OVERHANG OR ROOF cae A VENT EXHAUST OVERHANG ¥ Clearance to overhang per code Afigie 22.5° to r 45°off wall_-y as ao : For single pipe vent applications, install a 45 . degree elbow pointing & = downward ey ak BRACKET. oT en CF COUPLING 12 IN. SEPARATION BETWEEN bf ww jha-1~ S), pb J OF _ dee 12 in. G04.8rnm) MIN. Ground Level OR Snow Level WT COMBUSTION AIR AND wer ¢ BOTTOM A, fe BOTTOM OF VENT ne Mo A MAINTAIN 12 IN.
Vent Pipe Termination for Non-Direct Vent and Ventilated Combustion Figure 50 Air System Roof Termination (Preferred) er vent Maintain 12 in (305mm) minimum clearance above highest anticipated snow level maximum of 24in. (610mm) above. roof Abandoned masonry used as raceway (per code} 12 in. min. (805 mm)from overhang oF roof 6 in. (182mm) minimum clearance between wall and end of vent pipe. 10 in. (254mm) maximum pipe lengh Maintain 12 in.
4. lf a Tee is used on the termination (Alberta and Saskatchewan, when required), record the equivalent length of the Tee used. NOTICE ADDITIONAL INFORMATION ENE VENTING SYSTEMS FOR POLYPROPYL- Polypropylene venting systems include flexible vent pipe. These flexible vent pipes have a different equi- valent vent length than straight sections of PVC/ABS DWV vent pipe.
Optional Combustion Air Inlet Moisture Trap Figure 51 ——— TO CODE-APPROVED DRAIN OR CONDENSATE PUMP i Representative drawing only, some models may vary in appearance. Combustion Air and Vent Piping Insulation Guidelines NOTE: Use closed cell, neoprene insulation or equivalent. The vent pipe may pass through unconditioned areas. The amount of exposed pipe allowed is shown in Table 17 and Table 18. 1.
Use a flat blade screwdriver and tap on the knockout on opposite sides, where the knockout meets the casing. Fold the knockout down with duct pliers and work the knockout Upflow Configurations (CONTINUED) back and forth until it is removed. Trim any excess metal from the knockout with tin snips. The vent elbow can be rotated to the required location on the casing if necessary. See Figure 52 to rotate the vent elbow: 1.
Downflow Configurations (CONTINUED) Rotate vent elbow to required position. DOWNFLOW Horizontal Left Configurations (CONTINUED) vp, ALTERNATE COMBUSTION ae RIGHT - VENT CONFIGURATION Representative drawing only, some models may vary in appearance. A11312 A11328 HORIZONTAL LEFT - LEFT VENT CONFIGURATION Representative drawing only, some models may vary in appearance.
Installing the Vent Pipe Adapter and Horizontal Right Configurations (CONTINUED) Combustion Air Pipe Adapter 4. CARBON WARNING MONOXIDE POISONING Failure to follow this warning injury or death. Ryo HORIZONTAL RIGHT - LEFT VENT CONFIGURATION HAZARD result in personal To route the vent pipe and combustion air pipe through the furnace, the manufacturer supplied kit must be used.
Install the remaining vent and combustion air pipes as shown Optional below. NOTE: DO NOT USE THIS TECHNIQUE POLYPROPYLENE VENTING SYSTEMS. It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint. 1. Working from furnace to outside, cut pipe to required length(s). OO ONO af a 2. De-burr inside and outside of pipe. . Chamfer outside edge of pipe for better distribution of primer and cement. . Clean and dry all surfaces to be joined. .
Figure 57 | Combustion Two-Pipe and Single-Pipe Terminations Air Pipe Single and two pipe vent must be installed as shown in Figure 49 and Figure 50. Maintain the required separation distance between vents or pairs of vents as shown in Point elbow down towards back of furnace v Figure 49 and Figure 50 and all clearance shown or Figure 61.
Determine an appropriate location for termination kit using the guidelines provided in section “Locating The Vent Termination” in this instruction. 1. Cut two holes, one for each pipe, of appropriate size for pipe size being used. 2. Loosely install elbow in bracket (if used) and place assembly on combustion-air pipe. 3. Install bracket as shown NOTE: in Figure 46 and Figure 48. For applications using vent pipe option indicated by as shown in. Figure 46 and Figure 48 to avoid recirculation of gases.
Figure 58 Crawl Space Vent Termination L Ventilated Combustion Air intake pipe TT Z t 7 i ' i Pipe hangar 4 Ny 2 3” (76 mm) Ventilated Combustion Air 12” (805 mm) intake termination in crawl space CRAWL SPACE Figure 59 L1EO16A | Attic Vent Termination 4 Ventilated Combustion Air intake pipe ~ Vent through_,, roof flashing | 12” (305 mm) min. above higest level of insulation cM — | ES = VY Oe i — i ey ar IN | Ty] SN OLE) LN Oe 7 \ SSE uN} ATTIC 52 - PSEA) L Speci
Figure 60 Direct Vent Termination VENT TERMINAL Clearance OX) AIR SUPPLY INLET b=] AREA WHERE TERMINAL IS NOT PERMITED 25-24-65-2 NOTE: The following is based upon National codes for gas appliances, and is provided as a reference. Refer to Local codes which may supersede these standards and/or recommendations. item US. Installations (¢) Canadian Installations |) Clearance Description (per CAN/CSA B149.1) (per ANS! 2223.1/NEPA 54) . 12 in.
Figure 61 Other than Direct Vent Clearance - Ventilated Combustion Air Option a (X AIR SUPPLY INLET VENT TERMINAL ES AREA WHERE TERMINAL IS NOT PERMITED 25-24-65-2 NOTE: The following is based upon National codes for gas appliances, and is provided as a reference. Refer to Local codes which may supersede these standards and/or recommendations. Item Canadian Installations Clearance Description (per CAN/CSA B149.1) Clearance above grade, veranda, porch, deck, balcony or A B Cc U.S.
or DIRECT VENT (2-PIPE) AND NON-DIRECT VENT (1-PIPE) Unit Size BTU/Hr Vent Pipe Diameter (in.) oO) N} 713 100,000 (610 to 914) Ny] 2S] @] a) NY] aN ay ~j © ( ( ( ( 80,000 2001 to 3000 aa GIS Ol| al @| =| o 2} 2 BY @] @ & 250 235 175 110 15 10 gi O] 0 to 2000 (0 to 610) 15. (9.1) (6.1) ~j 2-1/2 40,000 60,000 80,000 100,000 120,000 140,000 40,000 60,000 420,000 | Altitude FT (M) 140,000 40,000 60,000 80,000 100,000 3001 to 4000 (914 to 1219) 120,000 140,000 40,000 177 (53.
Example 1 A direct-vent 60,000 BTUH furnace installed at 2100 ft. (640M). Venting system includes FOR EACH PIPE 100 feet (30 M) of vent pipe, 95 feet (28 M) of combustion air inlet pipe, (8) 90° long-radius elbows, (2) 45° long-radius elbows, and a factory accessory concentric vent kit. Can this application use 2-in.
5 eet 5 eters or Use DEDUCTIONS MEVL - Table 15 to determine allowable vent length for each application. Note: Vent sizing for Canadian installations over 4500 ft.
in Table 17 (F/G)9MXE Winter Furnace Input Design Temp °F (°C) Unconditio nsu pace - ent Pipe Length in Ft. &M 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) 100,000 -20 (-30) -40 (-40) 20 (-10) 0 (-20) 120,000 -20 (-30) -40 (-40) 20 (-10) 0 (-20) 140,000 -20 (-30) -40 (-40) 58 Specifications subject to change without notice.
Table in 18 & (F/G)9MXT| Winter Uncondition pace - ; Design _|Pipe Length High Heat | Temp °F (°C) Input . 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) -20 (-30) -40 (-40) 20 (-10) 0 (-20) 100,000 -20 (-30) -40 (-40) 20 (-10) 0 (-20) 120,000 -20 (-30) -40 (-40) International Comfort Product, LLC « PO Box 128 « Lewisburg, TN 37091 USA 440 01 4001 04 Specifications subject to change without notice.