Installation guide
|
Split
System
Condensers
Installation
Instructions
§
Start-Up
Procedure
Start-up
Procedure
1.
Close
electrical
disconnects
to
energize
system.
2.
Energize
crankcase
heater
on
units
so
equipped.
3.
Set
Thermostat
selector
switch
to
OFF.
4.
Set
room
thermostat
at
desired
temperature.
Be
sure
setpoint
is
below
indoor
ambient
temperature
for
cooling
and
above
indoor
ambient
for
heating.
5.
Setthe
system
switch
of
the
thermostat
on
COOL
and
fan
switch
for
continuous
operation
or
AUTO,
as
desired.
Operate
unit
for
15-20
minutes,
then
check
the
system
re-
frigerant
charge
if
it
was
necessary
to
adjust.
6.
After
the
refrigerant
charge
has
been
adjusted,
the
sys-
tem
is
now
ready
for
continuous
operation.
Final
Refrigeration
Charge
Adjustment
Before
any
adjustment
is
made
to
the
refrigerant
charge,
it
is
imperative
that
the
air
flow
characteristics
of
the
indoor
blower
be
established.
When
checking
indoor
air
flow,
it
is
important
to
remember
that
the
blower
will
deliver
a
higher
quantity
of
air
across
a
dry
coil
versus
a
wet
coil.
Blower
charts
are
calculated
with
a
dry
coil.
Recommended
air
flow
for
installations
of
cooling
units
and
heat
pumps
is
350-450
CFM
per
ton
(12,000
BTUH)
through
a
wei
coil.
Refer
to
indoor
unit
installation
instruc-
tions
for
proper
methods
of
determining
air
flow
and
blower
performance.
To
Check
System
Refrigerant
Charge
(Superheat
Method),
Cooling
Only
1.
Attach
an
accurate
temperature
sensing
device
to
the
suction
line
approximately
4”
-
6”
away
from
the
suction
line
service
valve.
The
temperature
sensing
device should
be
clamped
securely
to
the
suction
line,
on
a
horizontal
plane
(between
9
&
3
O'clock)
and
insulated.
Record
the
suction
line
temperature.
2.
Measure
and
record
the
suction
line
refrigeration
pres-
sure.
(Measure
at
the
suction
line
service
valve
gauge
port.)
Using
Temperature
/
Pressure
Chart
convert
this
pressure
to
the
saturation
refrigerant
temperature.
The
dif-
ference
between
actual
and
saturated
temperatures
is
the
amount
of
superheat.
Figure
9
-
Temperature
/
Pressure
Chart
Temper
|
PSIG
| Temper |
PSIG
|
Temper
|
PSIG
ature
°F]
R-22
|
ature°F|
R-22
|
ature°F|
R-22
-6
19.3
19
41.9
41
70.0
-4
20.8
20
43.0
42
71.4
-2
22.4
21
44.4
43
73.0
0
24.0
22
45.3
44
74.5
1
24.8
23
46.4
45
76.0
2
25.6
24
47.6
46
77.6
3
26.4
25
48.8
47
79.2
4
27.3
26
49.9
48
80.8
5
28.2
27
51.2
49
82.4
6
29.1
28
52.4
50
84.0
7
30.0
29
53.6
55
92.6
8
30.9
30
54.9
60
101.6
9
31.8
31
56.2
65
111.2
10
32.8
32
57.5
70
121.4
re
33.7
33
58.8
75
132.2
12
34.7
34
60.1
80
143.6
13
35.7
35
61.5
85
155.7
14
36.7
36
62.8
90
168.4
15
37.7
37
64.2
95
181.8
16
38.7
38
65.6
100
195.9
17
39.8
39
67.1
105
210.8
18
40.8
40
68.5
110
226.4
115
242.7
3.
Measure
and
record
the
outside
ambient
air
tempera-
ture.
4.
Optimum
performance
will
be
achieved
when
the
oper-
ating
charge
produces
15°-20°
F
suction
superheat
at
compressor
with
82°
F
outdoor
ambient
and
80°
F
dry
bulb
(67°
F
wet
bulb)
indoor
temperature
(ARI
“B”
test
condi-
tions)
at
rated
airflow.
If
these
conditions
cannot
be
ob-
tained,
compare
the
calculated
superheat
value
with
the
recommended
valves
given
in
Figure
10.
Figure
10
-
Recommended
Superheat
Values
Outside
Air
Superheat
°F
Temp
°
F
Variator
or
Piston
65
38
-45
75
27
-
33
85 20
-
25
95
10-15
105
2-6
Ifthe
actual
superheat
readings
are
higher
than
shown,
the
system
is
most
likely
under-charged,
and
charge
should
be
added.
Add
charge
in
4
ounce
increments,
and
recalcu-
late
superheat
values.
Continue
adjusting
charge
until
the
actual
superheat
approximately
matches
the
recom-
mended
values.
Ifthe
actual
superheat
readings
are
lower
than
shown,
the
system
is
most
likely
over-charged,
and
charge
should
be
removed.
Remove
charge
in
4
to
6
ounce
increments,
and
recalculate
superheat
values.
Continue
adjusting
charge
until
the
actual
superheat
approximately
matches
the
rec-
ommended
values.
Lo]