Installation guide

INSTALLATION INSTRUCTIONS R410A Split System Heat Pump
18 428 01 5106 02
Specifications subject to change without notice.
R410A QUICK REFERENCE GUIDE
R410A refrigerant operates at 50% 70% higher pressures than R22. Be sure that servicing equipment and
replacement components are designed to operate with R410A.
R410A refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
R410A systems should be charged with liquid refrigerant. Use a commercial type metering device in the
manifold hose.
Manifold sets should be 750 psig highside and 200 psig lowside with 520 psig lowside retard.
Use hoses with 750 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
R410A, as with other HFC refrigerants, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquid line filterdriers with rated working pressures less than 600 psig.
Do not install a suction line filterdrier in liquid line.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filterdriers and service valves with wet cloth when brazing.
A liquid line filterdrier is required on every unit.
Do not use with an R22 TXV.
If indoor unit is equipped with an R22 TXV, it must be changed to an R410A TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, break vacuum with dry nitrogen and replace all filterdriers.
Do not vent R410A into the atmosphere.
Do not use capillary tube indoor coils.
Observe all WARNINGS, CAUTIONS, NOTES, and bold text.
Copyright 2014 International Comfort Products
Lewisburg, TN 37091 USA