Owners manual
TPD/VPD Series HMI Device User Manual
Copyright © 2015 ICP DAS Co., Ltd. All Rights Reserved. Page: 10
1.4 Specifications
Note: Communication interface that is only for run time supports the following protocols:
1. For the case of RS-485, Modbus RTU Master and DCON Protocol Master (for ICP DAS I-7000
series modules) are supported. We provide API functions to open COM Port for sending/receiving
strings through RS-485.
2. For the case of Ethernet, Modbus TCP Master is supported. We provide API functions to
sending/receiving strings through TCP.
3. USB is used for firmware update only.
1.4.1 TPD-280/280U/283/283U Series Models
Models
TPD-280
TPD-280U
TPD-283
TPD-283U
CPU Module
CPU
32-bit RISC CPU
Memory Expansion
-
16 MB SDRAM /
8 MB Flash
-
16 MB SDRAM /
8 MB Flash
Real Time Clock (RTC)
-
Yes
-
Yes
Buzzer
Yes
Rotary Switch (0 ~ 9)
Yes
Communication Interface
Ethernet
-
RJ-45 x 1, 10/100 Base-TX
Serial Port
RS-485 (including Self-Tuner)
-
RS-485 (including
Self-Tuner)
USB 1.1 Client
-
Firmware updates
only
-
Firmware updates
only
MMI (Main Machine Interface)
LCD
2.8 TFT (Resolution 240 x 320 x 16), defective pixels <= 3
Backlight Life
20,000 hours
Brightness
160 cd/m2
Touch Panel
Yes
Reset Button
Yes
Electrical
Powered from Terminal Block
+10 ~ +30 VDC
-
+10 ~ +30 VDC
Powered from PoE
-
IEEE 802.3af, Class1 (48 V)
Power Consumption
1.2 W
Mechanical
Dimensions (W x L x H)
76 mm x 119 mm x 31 mm
Installation
Wall Mounting
Ingress Protection
Front Panel: IP40
Environmental
Operating Temperature
-20 ~ +70°C
Storage Temperature
-30 ~ +80°C
Ambient Relative Humidity
10 ~ 90% RH, non-condensing