 7000 Bus Converter User’s Manual (Version 1.8  Jan/2006, 7PH-006-18)  --------------- 68 
For example, the q7510, s7510 are used to isolate local modules 
from  nRS-485 network. If there is high energy transient on nRS-485 
network, all the local modules will be safe. 
Isolation Configuration (Strongly Recommended): 
If the RS-485 network is not over 100 meters, the terminated 
resistors are not needed. However, it may be necessary to insert two 
terminated resistors at both end of the RS-485 segment. It is not easy to 
calculate the value of a terminator resistor. The best way to do this is to 
use an oscilloscope to check the RS-485 signal directly. If the impedance 
match of RS-485 network is OK, the oscilloscope will show a very nice 
square wave. If these square wave signals are distorted, the user will 
need to insert two terminators at both end of the RS-485 segment. 
OK 
Resistor value of 
terminator is too small
Resistor value of 
terminator is too big 