User Manual
 7000 Bus Converter User’s Manual (Version 1.8  Jan/2006, 7PH-006-18)  --------------- 22 
WARNING!! ERROR CONDITION 2: if the p7520 uses the same DC 
power ground with nHost PC/PLC (for example, nHost PC/PLC 
provide non-isolated DC power source to p7520). In this situation, 
(1)  The nHost PC/PLC is common ground with power ground of p7520 
(2)  The power ground of p7520 is common ground with rRS-485 
Therefore the nHost PC/PLC is common ground with rRS-485 network. 
That is to say, there is no isolation between nHost PC/PLC and rRS-485 
network. So the nHost PC/PLC may be damaged if there is high voltage 
transient on rRS-485 network. 
OK CONDITION: If the DC power ground of p7520 or p7520R is not common 
to any module, the nHost PC/PLC will be isolated from rRS-485 network in 
all conditions. 
The power adapter PWR-24 is designed for single 7000 series modules 
only. The 24V DC output of the PWR-24 is isolated from its AC input. If the 
p7520 or p7520R is connected to the PWR-24, this PWR-24 cannot connect 
to the other module. Normally the nHost PC/PLC uses a switching power and 
the DC output of this power supply is also isolated from its AC input. Therefore 
the DC power ground of p7520 or p7520R is isolated from nHost PC/PLC. 
Therefore, the nHost PC/PLC is isolated from rRS-485 network in all condition. 
nHost PC/PLC is isolated 
from  rRS-485 network 
for  p7520 or p7520R in 
all condition 