User Manual
 7000 Bus Converter User’s Manual (Version 1.8  Jan/2006, 7PH-006-18)  --------------- 61 
5.3 I-7510AR: 
5.3.1 Pin Assignment and Specifications: 
Introduction 
I-7510AR is exactly the same as I-7510A except 
for the isolation site, The isolation site of I-7510A 
is  located  in  the  input  interface  circuit,  but  the 
isolation  site  of  the  I-7510AR is located in the 
input and output interface circuit. In other words, 
I-7510AR is three- way isolation repeater 
module.  
I-7510AR
RS-422/485 Repeter
( RS-485 )
( RS-485 ) ( RS-422 )
( RS-422 )
Variable Baud Rate
300,..9600,..115.2K
Variable Rate Format
Specifications 
• Input: RS-485/RS-422 
• Output: RS-485/RS-422 
•  Speed: “Self Tuner” inside, auto switching 
baud rate, from 300 to 115200 bps 
• Isolation voltage: Three-way 3000Vdc 
•  Connector: plug-in screw terminal block 
•  Power requirements: +10V to +30VDC 
•  Power consumption: 2.2W(Max) 