Install Instructions
ICM CONTROLS
www.icmcontrols.com
7313 William Barry Blvd., North Syracuse, NY 13212 
800.365.5525
LIAF280
ICM715
ELECTRICAL SHOCK HAZARD – Before installing this unit, turn off power at the main service panel by removing the fuse or 
switching the appropriate circuit breaker to the OFF position.
ECM to PSC Motor Controller
Installation Instructions
1. Drill four pilot holes using a #39 (7/64”) drill bit.
2. Mount the ICM715 circuit board using four #6 X 3/4” sheet 
metal screws.
3. Connect the low voltage harness to J1 through J5 and C.
4. CAUTION HIGH VOLTAGE – Connect the main power 
(120/208/240 VAC) to L,N and G with a 3/16” quick connect.
5. Connect the Common wire of the PSC motor (COM) to the 
COM terminal of the ICM715 with a 1/4” quick connect.
6. Select the speed you want to use and connect the wire for that speed to the 
ICM715 at the Speed terminal with a 1/4” quick connect.
7.WirethePSCmotor’scapacitorterminalstotheappropriatesizecapacitor
rated for the PSC motor.
8. Supply the 24 VAC “R” to the R terminal of the ICM715 using a 1/4” quick 
connect if an off delay is desired.
9. Select whether or not you wish to have an off delay of 3-minutes by 
removing the test jumper on P1 & P2 (default) and ensuring R is connected.
Once all connections are made, the ICM715 will take the 
signal outputs from an X13 or SelecTech constant torque 
ECM motor harness and output to a Single phase PSC 
motor to run the motor at a technician selected single 
speed. The technician can select a 3-minute delay by 
removal of a test jumper on P1 & P2 and placing 24 VAC 
on the “R” terminal. As shipped, the ICM715 will have 
a jumper installed on the test pins, which will provide a 
5-second OFF delay if “R” is connected to 24 VAC.
Mode of Operation
•  Motor Voltage: 120 VAC or 208-240 VAC
•  Input Control Voltage: 24 VAC
•  Input Frequency: 50-60 Hz
•  Maximum Blower Horse Power: 1 HP
•  Size: 4.0” x 2.2”
Specifications
QwikSwapX1
Replaces
C
L
G
N
J1
J2
J3
J4
J5
X13/SelecTech Harness
C
L
G
N
J1
J2
J3
J4
J5
R
COMSPEED
C
NO
COIL
TO
PSC
MOTOR
R13 R14
TEST
Connect R
P1
P2
ICM715
24 VAC “R” required for optional Off delay
X13/SelecTech
PSC Motor
Hi
Med
Low
Com
Cap
Cap
3.60”
1.80”
Capacitor
Wiring Diagram
Delay on Break Time (seconds) Jumper Between P1 and P2 Red Wir Connected to R
No delay Removed Removed
180 Seconds Removed Connected
5 Seconds (test mode) Connected Connected
No delay Connected Removed
Note: This table 
only applies if all 
connections are 
made and there is 
a thermostat call in 
place.
OFF Delay Time Table
DANGER !
Only trained personnel should install or service heating equipment. When working with heating equipment, be sure to read and understand all 
precautions in the documentation, on labels, and on tags that accompany the equipment. Failure to follow all safety guidelines may result in 
damage to equipment, severe personal injury or death.
CAUTI ON!
Failure to turn off gas and electric supplies can result in explosion, re, personal injury or death.