ICM493-60A
Input:
• 195-264 VAC
• 50/60Hz
Contact Ratings:
Voltage: 240 VAC
FLA: 60A
LRA: 360A
Control Operating Temperature:
Operating temperature: -40°F to 167°F (-40°C to 75°C)
Storage temperature: -40°F to 185°F (-40°C to 80°C)
LCD operating temperature: -4°F to 167°F (-20°C to 75°C)
Mechanical:
• Mounting: Four mounting holes in back of enclosure
• Enclosure: Weather resistant, NEMA 3R rated for outdoor installation
• Dimensions: 8”L x 10”W x 6”H
Parameters:
Line voltage: 200-240 VAC, adjustable
Over/under voltage setting: 5%-10%, adjustable
(under voltage limited to 195 VAC)
Anti-short cycle time delay: 0.5-10 minutes
Number of trials: 1-5, auto
Number of movistors: 0-5
Features
• Protects against over and under voltage,
rapid short cycling caused by transients, and
high-power surges
• Ideal for mini-splits or other condensing units
• Easy to view, backlit digital display
•BankofveL-Lsurgearresters
• Built-in 60A contactor
• NEMA Type 3R rated metal enclosure
• Easy installation and setup