LIS93-2
ICM409
THREE-PHASE LINE MONITOR
All features and specications subject to change without notice.
The ICM409 is a low cost
three-phase voltage monitor
with fault indicator.
Protects Against...
• Low Voltage • Power Interruptions
• High Voltage • Phase Loss
• Unbalanced Voltage • Phase Reversal
Features
• Adjustable delay-on-make timer for staggered starting
• Adjustable delay-on-break for anti-short cycle protection
• Adjustable universal voltage from 190 VAC to 480 VAC
• Adjustable voltage unbalance from 2-8% of the line
voltage
Status LED Indicators
• GREEN LED = Load ON • RED LED
• Solid = Phase reversal
• 1 ash = DOM time
• 2 ashes = Low voltage
• 3 ashes = High voltage
• 4 ashes = Unbalanced
voltage
DIN rail or surface mount
R
File # 53944
Mode of Operation
Designed in a small, easy-to-mount, surface mount or
DIN rail style case, the ICM409 continuously monitors the
incoming line voltage for errors. When the line voltage is
appropriate, the ICM409 closes a set of N.O. contacts and
lights a green LED. When the incoming voltage is outside
of the user’s set parameters, the N.O. contacts open
and the red light will ash a code for the particular fault
present. The control will also interrogate the line voltage
during the fault condition to avoid short cycling and
nuisance trips.
Specifications
User Selectable Universal Voltage
• 190-480 VAC
User Selectable Unbalanced Voltage
• 2-8%
• Trips after 6 seconds of unbalance condition
User Selectable Delay-on-Make (staggered start) Timer
• .1 to 5 minutes
User Selectable Anti-Short Cycle/ Delay-on-Break Timer
• .1 to 5 minutes
High/Low Voltage Cut-out
• High voltage cut-out setpoint + 12%
• Low voltage cut-out setpoint – 12%
• Detects condition within 100mS
Power/Phase Loss Detection
• Within 100mS
Phase Reversal Detection
• Detects phase reversal condition on power up
Relay Contact Ratings
• N.C. Contacts: 10A resistive @ 250 VAC
• N.O. Contacts: 10A resistive @ 250 VAC
Operating Frequency
• 50/60 Hz
Maximum Operating/Storage Relative Humidity
• 95% Non-condensing
Storage Temperature Range
• -40°C to +85°C
Connection Terminals
• Screw down terminals provide easy hookup for both line
voltage and control circuit wires
Conformal Coated Circuit
• Conformal coated circuit provides protection in extreme
environment conditions
Wiring Diagram
208
416
200
400
220
440
230
460
190
380
220
440
VOLT
ADJUST
%
Unbalance
8
7
6
5
4
3
2
2
1
.5
.1 5
4
3
DOB
MINUTES
DOM
MINUTES
2
1
.5
.1 5
4
3
PART NO.
ICM409
10 AMP @ 250 VAC
LOAD
STATUS
L1 L3L2
Control Voltage
3-Phase
Load
(optional alarm output)