Install Instructions
I C M
4 0 9
3-PHASE VOLTAHE MONITOR
LII266-2
www.icmcontrols.com
800-365-5525
ICM CONTROLS
7313 William Barry Blvd.
North Syracuse, NY 13212
WIRING DIAGRAM
L1 L3L2
Control Voltage
3-Phase
Load
(Optional alarm output)
SPECIFICATIONS
Conformal Coated Circuit: Conformal coated circuit provides use in extreme environment conditions
Connection Terminals: Screw-down terminals provide easy hookup for both line voltage and control circuit wires
Storage Temperature Range: -40°C to 85°C User Selectable Universal Voltage: 190-480 VAC
Operating Frequency: 50-60 Hz Power/Phase Loss Detection: Within 100 mS
Maximum Operating/Storage Relative Humidity: 95% Non-condensing
User Selectable Delay on Make (staggered start) Timer: .1 to 5 minutes
User Selectable Anti-Short Cycle (ASC)/Delay on Break Timer: .1 to 5 minutes
User Selectable Unbalance Voltage: 2 to 8% (trips after 6 seconds of unbalance condition)
Phase Reversal Detection: Detects phase reversal condition on power up
High/Low Voltage Cut-out: ± 12% – Detects within 100 mS
Relay Contact Ratings: N.C. Contacts: 10A resistive @ 250 VAC, N.O. Contacts: 10A resistive @ 250 VAC
Heavy Duty SPDT Relay Output: 10 AMP output to operate control circuitry
INSTALLATION MODE OF OPERATION
1. Disconnect or turn off power.
2. Tapoffthemain3-phaselinevoltageandruneld-installedwirestothe
ICM409 control.
3. Theeld-installedwiresshouldhave1ampfuses(ratedforthevoltage
being used) installed in series with the ICM409.
4. Connecttheeld-installedwirestotheL1,L2,andL3screw-down
connections.
5. Set the DOM time delay to a minimum for testing purposes.
6. Break one line of the control circuit and connect to the COM and N.O.
screw-down connections on the ICM409.
7. The N.C. connection can be used as an alarm output.
8. Reapply or reconnect power.
9. After the DOM time delay, the unit should energize and the Green
(load) LED should light.
10. If the Red (status) LED is on solid, reverse any 2 line voltage wires at
the ICM409. DO NOT CHANGE THE WIRING SEQUENCE TO THE
CONTACTOR OR MOTOR/COMPRESSOR.
11. IftheRed(status)LEDisashing,makesurethevoltageand
unbalance levels are set correctly.
12.Setallparametersaccordingtomanufacturer’sspecications.
Designed in a small, easy-to-mount, DIN
Rail style case, the ICM409 continuously
monitors the incoming line voltage for errors.
When the line voltage is appropriate, the
ICM409 closes a set of N.O. contacts and
lights a green LED. When the incoming
voltage is outside of the user-set parameters,
the N.O. contacts open up and the red
LEDwillashacodefortheparticularfault
present. The control will also interrogate the
line voltage during the fault condition to avoid
short cycling and nuisance trips due to noise.
STATUS LED INDICATORS
• GREEN LED = Load ON
• RED LED:
• Solid = Phase reversal
•1ash=DOMtime
•2ashes=Lowvoltage
•3ashes=Highvoltage
•4ashes=Unbalancevoltage