User Guide
5
1.  The Heat Pump terminals accept the 24 VAC signal from the reversing 
valve holding coil. Make a parallel connection from the reversing valve to 
the HP terminals.
   Note: Do not apply a voltage higher than 30 VAC 
to the HP terminals.
2.  If the Heat Pump is in the Heating mode and the reversing 
valve is energized, then the Heat Pump Select jumper must 
be in the Default (N.O.) position.
3.  If the Heat Pump is in the Heating mode and the reversing 
valve is not energized, then the Heat Pump Select jumper 
must be in the N.C. position.
Connections for Heat Pump Systems
N.O.
N.C.
Temperature 
Probe
24 VAC Connect Parallel to 
24 VAC Reversing Valve
Additional 
Probes
Probe S1
HP
Heat Pump 
Select Jumper 
Default Position