User Guide

Power supply. Provide disconnect means and
overload protection as required. Make sure
L1 and L2 are not reversed.
Remove jumper quick connect from ICM283.
Cut wire at circuit board and discard.
Alternate limit controller location.
Sensor rod will be present if remote sense.
Cut 3/16” quick connect off wire and replace
with a 1/4” quick connect (supplied).
Power supply. Provide disconnect means and
overload protection as required. Make sure
L1 and L2 are not reversed.
Use adapter plug with black and orange
wires (supplied).
When S89/S890 is a remote sense model,
remove jumper quick connect from ICM283.
Cut wire at circuit board and discard.
Connect flame rod lead wire to SENSE.
Alternate limit controller location.
Cut 3/16” quick connect off wires and replace
with a 1/4” quick connect (supplied).
Cut 3/16” quick connect off wires and replace
with a 3/16” quick connect (supplied).
Hot Surface Ignitor
L1 (Hot)
Adapter
Black
Orange
L2
Combination
Gas Control
Flame
Sensor
Thermostat
or Controller
MV MV
Burner
Ground
Limit
Controller
LPP135
Hot Surface Ignitor
L1 (Hot)
L2
Combination
Gas Control
Flame
Sensor
Thermostat
or Controller
MV MV
Burner
Ground
Limit
Controller
LPP135
• EXPLOSION HAZARD!
• Incorrect installation can cause death, severe injury or equipment damage!
• Thiscontrolmoduleshouldbeinstalledbyqualiedtechnicianscapableofworkingwith
liquidpropane,naturalgasandhighvoltageelectricity
IMPORTANT:
1. Allwiringmustcomplywithapplicableelectricalcodesandordinances.
2. Hotsurfaceigniterleadwiresshouldnotbeallowedtorestagainstgroundedmetalsurfaces.
3. AcommongroundisrequiredfortheICM283andthemainburner.The24V(GND)terminal
internallygroundsonesideofthetransformer.Anyauxiliarycontrolsorlimitsmustnotbeinthe
groundedleg.Inaddition,theapplianceshouldbeearth-grounded.
4. MakesurethetransformerhasadequateVA.TheICM283 ignitionmodulerequires0.4Aat24
VAC.Addthecurrentdrawsofallotherdevicesinthecontrolcircuit,includingthepilotand
ICM283 Wiring Diagrams
ICM283
Installation, Operation & Application Guide
For more information on our complete range of American-made
products – plus wiring diagrams, troubleshooting tips and more,
visit us at www.icmcontrols.com
WARNING
•EXPLOSION HAZARD!
•Can cause death, severe injury or equipment damage!
•Thiscontrolmoduleshouldbeinstalledbyqualiedtechnicianscapableof
workingwithliquidpropane,naturalgasandhighvoltageelectricity.
Specifications
• Control Voltage:24V,60Hz
• Maximum Valve Contact Rating:2A
• Current Draw:.4Aplusvalveload
• Hot Surface Igniter Voltage:120VAC,60Hz
• Contact Rating At 120 VAC:5A
• Prepurge:32seconds.
• Igniter Warm up:34seconds
• Flame Failure Response Time:1.5secondsmaximum
• Between Trial Purge:96seconds(threetrialsettingonly)
• Sensor:Aseparatesensorisrequiredforremotesensingapplications
• Ignition Sequence:Determinedbythedipswitchposition
• Ambient Operating Temperature:-40°Fto+175°F(-40°Cto+79°C)
Application
TheICM283UniversalHotSurfaceIgnitionModuleisareplacementforawiderangeofhotsurface
ignitionmodules.TheICM283providescontrolofadirectignitionsystemusinga120VAChot
surfaceigniter.TheICM283replacesexistingamerecticationtypehotsurfaceignitionmoduleswith
thefollowingcharacteristics:
• 120VAC(upto5A)timedhotsurfaceignition
• Singlerod(localsense)ordualrod(remotesense)hotsurfaceignitionsystems
• Oneorthreeignitiontrialsperheatcall
• Four-secondorseven-secondignitiontrials
• Prepurgeof32secondsorless
• Upto96secondsbetweentrialpurgetimes(three-trials)
• NaturalorLPgas
TheICM283packagecontainstheICM283controlmodule,theapplicationguide,andtheaccessories
requiredtoadapttooldersystems.
Installation Warnings
1. Read these instructions carefully.FailuretofollowtheseInstructionscoulddamagethemodule
orcauseahazardouscondition.Installermustbeatrained,qualiedservicetechniciancapableof
workingwithliquidpropane,naturalgasandhighvoltageelectricity.
2. VerifythattheICM283isthecorrectreplacementforthemoduleinyoursystem.
3. Never installwherewatercanood,driporcondenseonthemodule.Neveruseamodule
thathasbeenwet.Replaceit.Iftheignitionmodulegetswet,itcanmalfunction,leadingto
accumulationofexplosivegas.Donotattempttodisassembleorcleanthemodule.Improper
reassemblyandcleaningcancauseamalfunctionorunreliableoperation.Ifamodulemustbe
mountedwhereitcanbeexposedtomoistureorwater,provideasuitablewaterproofenclosure.it
isbesttomountthecontrolwiththeterminalsdowntoavoidwatergettingontomodule.
4. Disconnect the powersupplybeforebeginningwiringtopreventelectricalshockorequipment
damage.
5. Turn off the gas supplybeforestartingtheinstallation.Ifyousmellgasorsuspectagas
leak,turnoffgasatthemanualservicevalveandevacuatethebuilding.Donottrytolightany
appliance;donottouchanyelectricalswitchortelephoneinthebuildinguntilyouaresurenogas
remains.
6. Do not lightthepilotoroperateelectricswitches,lightsorappliancesuntilyouaresurethe
applianceareaisfreeofgas
7. Usingthewirelabelsprovided,labelallthewiresbeforedisconnecting.Wiringerrorscancause
improperapplianceoperation,ignitionmoduledamageanddangerousconditions(suchas
bypassingsafetyfeatures).
8. Improperlocationofthe120VAChotsurfaceigniteroranyamesensingrodcanresultin
appliancemalfunction.
9. Neverattempttorelocatethe120VAChotsurfaceigniterortheamesensingrodfromtheoriginal
positionestablishedbytheappliancemanufacturer.
10.Besurethe120VAChotsurfaceigniterortheamesensingrodisreplacedinexactlytheoriginal
positionafterremovalforinspection,serviceorreplacement.
Remove Old Module
Disconnectthepowersupplyandturnoffgasatshutoffvalvebeforedoinganyworkontheunit.
Disconnectandtagthewiresfromtheoldmoduleusingthewirelabelsprovided.Removetheold
modulefromitsmountinglocation.
ICM283 Mount Instructions
MounttheICM283Moduleinthesamelocationastheoldmodule.Protectthemodulefromexposure
towater,moisture,corrosivechemicalsandexcessivedustandgrease.Assurethatambient
temperatureatthemoduleiswithintherangelistedabove.
Mountthemodulewiththeterminalsdowntoprotectfromdrippingwateranddust.Themodulecan
alsobemountedwithterminalsoneitherside.Donotmountwiththeterminalspointingup.Whenit
isnecessarytodrillnewmountingholes,usetheICM283asatemplatetomarkthemountinghole
pattern.Drillnewholesasrequired.Usecautionwhiledrillingtoavoiddamagingwires,gaslines,
heatexchanger,etc.FastensecurelywithfourNo.6-32machineorNo.8sheetmetalscrews.
Set the Dip Switches
Youmustsetthedipswitchescorrectlytomatchyoursystem.SeeICM283CrossReferenceCharton
otherside.
ICM283 Terminal Cross References
ICM283 S89/S890 HS780
GND(Burner) GND(Burner) TR(GNDClip)
24VAC(GND) 24VAC(GND) GND
Valve(GND) Valve(GND)
24VAC 24VAC TH
Valve Valve Valve
L2 L2 L2
L1 L1 L1
HSI HSI IGN
HSI HSI IGN
Sense SEN RS
mainvalvesinthegascontrol,andmultiplyby24todeterminethetotalVArequirementof
thesecomponents.Addthistotalto9.6VA(fortheignitionmodule).Theresultistheminimum
transformerVArating.UseaClassIItransformerwhenreplacementisrequired.
5. CheckthatL1(hot)andL2(neutral)arewiredtotheproperterminals.
6. ConnectthewirestotheICM283IgnitionModuleasshown.Makesurethatthesystemis
adequatelygrounded.Whereachangeinquickconnectisrequired,cutofftheoriginalquick
connect,striptheleadwireandrmlycrimpinplacetheproperquick-connectsupplied.
Notes:If you smell gas or suspect a gas leak, turn off gas at the manual service valve and evacuate
the building. Do not try to light any appliance; do not touch any electrical switch or telephone
in the building until you are sure no gas remains.
The Gas leak Test must be done for initial installation and any time work is done involving
the gas lines or equipment.
A B C D
Typical hookup when
ICM283 replaces
White-Rodgers 50E/F47.
Typical hookup when
ICM283 replaces
Robertshaw HS780 and
S89/S890.
• Hotsurfaceignition(HSI)module
• Single/dualrodsensing
capabilities
• Forgasfiredfurnaces,boilers
andotherheatingapplications
• Switchselectablelockouttimes,
ignitiontrials
• WorkswithbothNaturalandLP
gassystems
• DiagnosticLEDtoaidin
troubleshooting