Product Overview
ICM283
GAS IGNITION CONTROL
LIS208-1
Low cost, direct replacement ignition control
Features
•Hotsurfaceignition(HSI)module
•Single/dualrodsensingcapabilities
•Forgasfiredfurnaces,boilersand
other heating applications
•Switchselectablelockouttimes,
ignition trials
•WorkswithbothNaturalandLPgas
systems
•DiagnosticLEDtoaidintroubleshooting
• Honeywell:S89,S890,S8910U-1000
• Robertshaw:HS780
• White-Rodgers:50E47,50F47
Replaces
Specifications
Electrical
• Input Voltage:120and24VAC@60Hz
–HSI:120V,5Amaximum
–Valve:24V,2Amaximum
–Total:24VLoad=0.4+valveload
Timing
• Pre-Purge Time:32seconds
• Trial Time:4or7seconds(switchselectable)
• Ignition Trials to Lockout: 1or3seconds
(switchselectable)
• Flame Sense:Singleordualrod
• Gas Type:NaturalorLP