LIS138-1
ICM220
LOCKOUT PROTECTION RELAY
All features and specifications subject to change without notice.
The ICM220 is a low cost lockout protection
module that helps eliminate nuisance
lockouts due to impedance relay failure.
SpecificationsMode of Operation
Upon application of power with the safety switches
closed, the load will energize. If any of the safety switches
open for longer than 600 ms, the fault light will come on
and the load will stay de-energized regardless of the state
of the safety switches. Power must then be removed for
100 ms and safety switches must be closed in order to
reenergize the load, upon which the fault light will be off.
Input
Voltage: 18-30 VAC
Frequency: 50/60 Hz
Output
Relay: SPDT
Relay Contacts: 2 amps maximum @ 30 VAC resistive
Power Consumption: 2 watts maximum during lockout
Dimensions
.765
1.1502.000 SQ.
1.000
TYP.
1/4” Quick Connects.256 Diameter
Mounting Hole
Features
Low cost lockout relay
Safety switch monitoring
Alarm output during lockout
Helps eliminate nuisance lockouts
Replaces impedance relays 83 and 93
Wiring Diagram
24 VAC RC
3 1
2
4
Safety Switches
Load
Contactor
Fault
Light

Summary of content (1 pages)