User Guide
LII55-1
ICM
207/208/209
DELAY ON BREAK
APS
6333 Daedalus Drive, Cicero, N.Y. 13039
visit us on the web at:
www.icmcontrols.com
800-365-5525
ICM CONTROLS
Compressor
Lockout
•
3 or 5 minutes xed, 10 minutes adjustable
•
Works with anticipator type thermostats
WIRING DIAGRAM
INSTALLATION
1.
Disconnect power.
2.
Connect terminals as shown in the wiring
diagram below.
3.
Select the desired time delay
(adjustable models only).
4.
Reapply power, check operation.
MODE OF OPERATION
Upon initial thermostat closure, the load is
energized. When the thermostat opens or there
is a loss of power, the load is de-energized and
the delay period begins. The compressor will
not start again during the delay period.
SPECIFICATIONS
Input
•
Voltage:
18-240 VAC
•
Frequency:
50-60 Hz
Output
•
Output Ratings:
– Maximum:
1 amp
– Minimum:
40 mA
– Inrush:
10 amps
Time Delay
•
Fixed:
3 or 5 minutes
•
Adjustable:
10 minutes
Contactor
Compressor
Thermostat Switch
Input
Voltage
TIMING DIAGRAM
Time Delay Initiated
Load
Energized
Load
Energized
Time
Delay
Load
Voltage
0
V
0
V
Input
Voltage
Switch Open or
Loss of Power
Switch
Closed
Time
Time