Manual
ICM
203
DELAY ON BREAK
6333 Daedalus Drive, Cicero, N.Y. 13039
visit us on the web at: www.icmcontrols.com
800-365-5525
ICM CONTROLS
LII34
18-240 VAC, 2-Wire
ANTI-SHORT CYCLE/
LOCKOUT TIMER
VPS00C
INSTALLATIONMODE OF OPERATION
•
Knob adjustable from .03-10 minutes
•
Works with anticipator type thermostats
WIRING DIAGRAM
Y
R
C
T’STAT
Contactor
Compressor
Control
Transformer
Line
Voltage
1. Disconnect power.
2. Connect terminals in series with the
starting device as shown in the wiring
diagram below.
3. For 24 VAC circuits, apply control as
packaged. For 120/240 VAC circuits,
cut the jumper wire.
4. Select the desired time delay.
5. Reapply power, check operation.
With application of power, the load is
energized. When the thermostat opens or
when there is a loss of power, the load is
de-energized and the delay period begins.
The compressor will not start again during
the delay period. The ICM203 provides
true thermostat interruption protection,
even in the presence of a trickle current.
SPECIFICATIONS
Input
• Voltage: 18-240 VAC
• Frequency: 50/60 Hz
Output
• Output Ratings:
– Maximum: 1.5 amps
– Minimum: 40 mA
– Inrush: 15 amps
Time Delay
• .03-10 minutes adjustable
TIMING DIAGRAM
Time Delay Initiated
Load
Energized
Load
Energized
Time
Delay
Load
Voltage
0
V
0
V
Input
Voltage
Switch Open or
Loss of Power
Switch
Closed
Time
Time