Installation Manual
ICM
175
BYPASS TIMER
Low Pressure Switch
Bypass, Low Ambient
Startups, 18-240 VAC
•
Knob adjustable from 10-1,000 seconds
•
Ideal for “winterstart” kits
WIRING DIAGRAM
Input
18-240 VAC
21 3
Load
INSTALLATIONMODE OF OPERATION
SPECIFICATIONS
Input
• Voltage: 18-240 VAC
• Frequency: 50-60 Hz
Output
• OutputRatings:
–Maximum: 1 amp
–Minimum: 40 mA
–Inrush: 10 amps
Time Delay
• 10-1,000 seconds
TIMING DIAGRAM
1. Disconnect power.
2. Connect terminals as shown in the
wiring diagram below.
3. Select the desired time delay.
4. Reapply power, check operation.
When power is applied to the input,
regardless of the state of the pressure
switch, the load is energized and timing
begins. After the timing delay is complete,
the pressure switch will control the load. The
control is reset by removing power during or
after the time delay.
Time Delay
Load Energized
0
V
Input
Voltage
Load
Voltage
Time
Time