Installation Manual
ICM
103
DELAY ON MAKE
HMPS00CM
SPECIFICATIONS
Input
• Voltage: 18-240 VAC
• Frequency: 50-60 Hz
Output
• OutputRatings:
–Maximum: 1 amp
–Minimum: 40 mA
–Inrush: 10 amps
Time Delay
• 1-1,023 seconds, switch settable in 1-second increments
INSTALLATIONMODE OF OPERATION
•
Switch settable from 1-1,023 seconds
•
Works with anticipator thermostats
TIMING DIAGRAM
1. Disconnect power.
2. Connect terminals in series with the
starting device as shown in the wiring
diagram below.
3. Select the desired time delay.
4. Reapply power, check operation.
When power is applied to the input, the
time delay begins. After the time delay is
complete, the load energizes and remains
energized as long as power is applied. The
control is reset by removing power during or
after the time delay period.
0
V
Load
Voltage
0
V
Input
Voltage
Transfer
Load
Energized
Time Delay
Time
Time
WIRING DIAGRAM
Y
R
C
T’STAT
Contactor
Compressor
Control
Transformer
Line
Voltage
7313 William Barry Blvd.
North Syracuse, NY 13212
ICM CONTROLS 800.365.5525
www.icmcontrols.com
LII059-1