ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
21
CONTROL BOARD - BIN FULL
As the ice slab falls from the Evaporator, the Curtain(s) is pushed out, contacts of the Magnetic Curtain
Switch(s) open as the ice slab falls. If the Curtain(s) remains open for 30 seconds, the unit will shut down
on a full bin. All RELAY LED’s (R1 - R6) will go off. If the storage is not full, the unit will restart the next
cycle. See pg. 28.
Anytime the unit is turned off or cycles off on a full bin due to aCurtain Switch being open for 30 seconds
and/or an added Bin Thermostat remaining open for 90 seconds, the unit will not restart for 3 minutes,
preventing a Compressor short cycle.