ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
19
CONTROL BOARD - HARVEST
After the Purge Valve and Water Pump de-energize, the Water Inlet Valve will remain open for 20 sec-
onds, partially filling the SUMP in preparation for the next Freeze Cycle (R2, R3, and R4, are illuminated
on Air and Water Cooled units, R1 is also energized on Remotes.) The Low Float Switch will go off as the
water level rises.
The Hot Gas Valve and Harvest Assist will remain energized for the remainder of the Harvest Cycle.