Service Manual
ELEVATION SERIES CIM CUBERS SEQUENCE OF OPERATIONS
18
CONTROL BOARD - HARVEST
After the contacts of the Low Float Switch close, the Harvest Cycle starts by energizing the Hot Gas Valve,
Harvest Assist, Purge Valve AND Water Inlet Valve (R2, R3, R4, R5 and R6 are illuminated on Air and
Water Cooled units, ALL Relays are energized on Remotes.) The Purge Valve will close after 7 seconds.
NOTE: Minimum Freeze time is 20 seconds. Maximum freeze time is 5.5 minutes.
BROWN
BLUE
VIOLET
BLACK
RED
TAN
PINK
YELLOW
= Illuminated LED
WHITE
WHITE
BLUE w/ WHITE
BLUE w/ RED
BLUE
12V DC Switches
Line Voltage
Components
R1 R2 R3 R4 R5 R6