Datasheet
IBM 6000VA LCD 4U Rack UPS 4
Specifications
Table 2 lists the specifications for the three 6000VA UPS models.
Table 2. Specifications (Part 1 of 2)
Specification IBM 6000VA LCD 4U Rack UPS
(200V/208V)
IBM 6000VA LCD 4U Rack UPS
(230V)
IBM part number 5395-6AX 5395-6KX
VA/Watts rating 6000 VA / 5600W 6000 VA / 5600W
Nominal output voltage (Vac) 208V AC 230V AC
Load groups Two Two
Output connections Two NEMA L6-30R
Four IEC 320 C19
Four IEC 320 C19
Six IEC 320 C13
Nominal output voltage regulation 184-228V (208V) 208-253V (230V)
Input
Nominal input voltage
(auto sensing at first power-up)
208V 230V
Input frequency (auto sensing) 50/60 Hz +/- 3 Hz 50/60 Hz +/- 3 Hz
Input connection Type Hard-wired to terminal block Hard-wired to terminal block
Included line (input) cords None None
Input voltage range, mains
operations
155-255V for 208V 160V-286V for 230V
Batteries
Typical backup times See Table 3 See Table 3
Battery type Valve Regulated Lead Acid (VRLA)
–
maintenance-free, sealed, leak-proof
Optional External Battery Pack Yes, 69Y1984 Yes, 69Y1984
Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load
Communications and management
USB port Yes Yes
RS-232 serial port Yes Yes
Ethernet port Optional using Network Management Card, 46M4110
Environmental Monitoring Probe Optional Environmental Monitoring Probe, 46M4113
Surge Protection and Filtering
Surge energy rating 1300 Joules 1300 Joules
Filtering ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)