Datasheet

3
IBM Systems and Technology Group
Data Sheet
Simplified deployment
The IBM 3000 is a rack-ready UPS product that supports
preconfigured shipment in an IBM rack. The modular design
of the UPS and EBM allows for scalability and versatility.
IBM UPS solutions are designed by IBM and manufactured
to IBM’s demanding specifications by Eaton Corporation,
a recognized global leader in power management. This
longtime partnership enables you to receive IBM’s renowned
service, support and warranty protection worldwide, coupled
with Eaton’s expertise in UPS and power management soft-
ware solutions. IBM power protection solutions integrate into
both IBM Systems Director and Tivoli® products.
IBM 3000 Rack UPS technical specifications
IBM model number LCD 3U Rack UPS LCD 3U Rack UPS LCD 3U Rack UPS
(100/120 V) (200/208 V) (230 V)
IBM part number 53953AX 53953JX 53953KX
VA/Watts rating 2880 VA/2700 W (120 V) 3000 VA/2700 W 3000 VA/2700 W
2300 VA/2300 W (100 V)
Nominal output voltage (V ac) 100/120 V 208 V 230 V
(autosensing at first power-up)
Waveform type Sine wave
Output connections (All output (1) NEMA L5-20R (2) NEMA L6-20R (2) IEC 320 C19
receptacles are controllable via (2) NEMA 5-20R (2) IEC 320 C19 (8) IEC 320 C13
Two-Load Groups (segments)) (2) IEC 320 C19 (2) IEC 320 C13
(2) IEC 320 C13
Nominal output voltage (V ac) 92 - 108 V (100 V) 184 - 228 V (208 V) 208 - 253 V (230 V)
106 - 132 V (120 V)
Input
Nominal input voltage 100/120 V 208 V 230 V
Input frequency (autosensing) 50/60 Hz +/- 3 Hz
Input connection type NEMA L5 - 30P IEC 320 - C20 IEC 320 - C20
Input cords NEMA L5 - 30P 2.0 m IEC 320 C19 to NEMA L6-20P, 4.3 Optional Country Specific Line
m Cords
IEC 320 C19 to LP-3, 4.3 m
(Taiwan)
Input voltage range, mains 84 - 121 V for 100 V 155 - 255 V for 208 V 160 - 286 V for 230 V
operations 97 - 145 V for 120 V
Batteries
Typical backup times 14 minutes (at 50% rated W)
5 minutes (at rated W)
Battery type Valve Regulated Lead Acid (VRLA)—maintenance free, sealed, leak proof
Optional external battery pack Yes
Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load