Datasheet

IBM 2200VA LCD 2U Rack Uninterruptible Power Supply for IBM System x 6
Table 3. Specifications (continued)
Specification IBM 2200VA LCD 2U Rack UPS
(100V/120V)
IBM 2200VA LCD 2U Rack UPS
(230V)
Communications and management
USB HID port Yes Yes
RS-232 serial port Yes Yes
Ethernet port Optional using Network Management Card, 46M4110
Environmental Monitoring Probe Optional Environmental Monitoring Probe, 46M4113
Management software included IBM UPS Manager
Control panel Intelligent three-button, dual color, backlit graphical LCD displays vital UPS
status in nine languages
Audible alarm Alarm when on battery: Distinctive low-battery alarm
Remote Power Off (REPO) REPO port
Surge Protection and Filtering
Surge energy rating 1200 Joules 2400 Joules
Filtering ANSI/IEEE C62.41; 1991 CATEGORYB3 (SURGE)
The following tables list the expected period that the UPS will operate solely on batteries. Table 4 is for
the 100V/120V model and Table 5 is for the 230V model.
Table 4. IBM 2200VA UPS (100V/120V) runtime chart
Load Run time on batteries
Load (%) Load (VA) Load (Watts) Run time with standard
internal battery only
Run time with internal
battery plus External
Battery Module (EBM)
25% 500 VA 500 W 42 minutes 143 minutes
50% 969 VA 969 W 14 minutes 66 minutes
75% 1450 VA 1450 W 11 minutes 43 minutes
100% 1920 VA 1920 W 5 minutes 28 minutes
Table 5. IBM 2200VA UPS (230V) runtime chart
Load Run time on batteries
Load (%) Load (VA) Load (Watts) Run time with standard
internal battery only
Run time with internal
battery plus External
Battery Module (EBM)
25% 550 VA 500 W 41 minutes 138 minutes
50% 1100 VA 968 W 14 minutes 64 minutes
75% 1650 VA 1450 W 10 minutes 40 minutes
100% 2200 VA 1920 W 5 minutes 28 minutes