Datasheet

IBM 2200VA LCD 2U Rack Uninterruptible Power Supply for IBM System x 5
Specifications
Table 3 lists the specifications for the two 2200VA LCD 2U Rack UPS models.
Table 3. Specifications (Part 1)
Specification IBM 2200VA LCD 2U Rack UPS
(100V/120V)
IBM 2200VA LCD 2U Rack UPS
(230V)
IBM part number 5395-2AX 5395-2KX
VA/Watts rating 1920 VA/1920W (120V)
1500 VA/1500W (100V)
2200 VA/1920W
Nominal output voltage (Vac) 100/120V AC 230V AC
Load groups Two Two
Output connections Six NEMA 5-20R
Two IEC 320 C19
Two IEC 320 C13
Two IEC 320 C19
Eight IEC 320 C13
Nominal output voltage regulation 92-108V (100V)
106-132V (120V)
208-253V (230V)
Input
Nominal input voltage
(auto sensing at first power-up)
100/120V 230V
Input frequency (auto sensing) 50/60 Hz +/- 3 Hz 50/60 Hz +/- 3 Hz
Input connection Type IEC 320-C20 IEC 320-C14
Input cords IEC 320 C19 to NEMA 5-20P 4.3 m Optional country specific line cords
(See Table 2)
Input voltage range, mains
operations
84-121V for 100V
97-145V for 120V
160V-286V for 230V
Batteries
Typical backup times See Table 4 See Table 5
Battery type Valve Regulated Lead Acid (VRLA)
maintenance-free, sealed, leak-proof
Optional External Battery Pack Yes, 46M410. Maximum of one EBM can be connected to the UPS.
Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load