Installation manual

A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 59 © IBM Corporation 2012
IBM iDataPlex Chassis Label Rating Continued
Chassis
Slot Configuration
Power
Supply
Wattage
Number Power
Supplies
Chassis Rating
Standard
Max
2U Flex Chassis
(7831, 6385)
2 Planars
Dual 750W
Power
Supply
2
2
200VAC 3.90A
208VAC 3.80A
220VAC 3.53A
230VAC 3.38A
240VAC 3.22A
2U Flex Chassis
(7831, 6385)
1 Planar with I/O Tray
Dual 750W
Power
Supply
2
2
200VAC 2.37A
208VAC 2.27A
220VAC 2.15A
230VAC 2.05A
240VAC 1.97A
2U Flex Chassis
(7381, 6385)
1 Planar with Storage
Tray
Dual 750W
Power
Supply
2
2
200VAC 2.43A
208VAC 2.32A
220VAC 2.19A
230VAC 2.11A
240VAC 1.99A
3U Storage Chassis
(7834, 6386)
Dual 750W
Power
Supply
2
2
200VAC 2.89A
208VAC 2.76A
220VAC 2.61A
230VAC 2.51A
240VAC 2.39A
IBM xSeries Server Label Rating
Server
Power
Supply
Wattage
Power
Supplies
Standard
Power
Supplies
Max
100-127VAC
Rating / Server
200-240VAC
Rating / Server
Redundant
@
100-127V
x100
310W
1
1
4.5A
2.25A
-
x206
400W
1
1
5.5A
2.75A
-
x206
430W
1
2
5.5A
2.75A
Yes
x226
530W
1
1
7A
3.5A
-
x226
514W
1
2
7A
3.5A
Yes
x236
670W
1
2
8.93A
4.465A
Yes
x255
370W
2
4
10A
5A
Yes
x260
775W
2
3
18.4
9.2A
No
x306
350W
1
1
4.3A
2.15A
-
x335
332W
1
1
4A
2A
-
x335
411W
1
1
3.5A
1.75A
-
x336
585W
1
2
5.5A
2.75A
Yes
x346
625W
1
2
8.3A
4.15A
Yes
x366
1300W
1
2
15.75A
7.875A
No
x445
1200W
2
2
9.5A
4.75A
No
x445 16-way
1200W
4
4
19A
9.5A
No
x460
1300W
2
2
15.75A
7.875A
No