Installation manual

A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 58 © IBM Corporation 2012
IBM iDataPlex Chassis Label Rating
Chassis
Slot Configuration
Power
Supply
Wattage
Number Power
Supplies
Chassis Rating
Standard
Max
2U Flex Chassis
(7831, 6385)
2 Planars
900W High
Efficiency
1
1
100VAC 8.62A
110VAC 7.71A
115VAC 7.35A
120VAC 7.00A
127VAC 6.63A
200VAC 4.19A
208VAC 3.98A
220VAC 3.81A
230VAC 3.61A
240VAC 3.46A
2U Flex Chassis
(7831, 6385)
1 Planar with I/O Tray
900W High
Efficiency
1
1
100VAC 5.90A
110VAC 5.28A
115VAC 5.01A
120VAC 4.83A
127VAC 4.61A
200VAC 2.93A
208VAC 2.83A
220VAC 2.68A
230VAC 2.57A
240VAC 2.47A
2U Flex Chassis
(7381, 6385)
1 Planar with Storage
Tray
900W High
Efficiency
1
1
100VAC 5.54A
110VAC 4.89 A
115VAC 4.67A
120VAC 4.44A
127VAC 4.20A
200VAC 2.67A
208VAC 2.56A
220VAC 2.43A
230VAC 2.33A
240VAC 2.24A
3U Storage Chassis
(7834, 6386)
900W High
Efficiency
1
1
100VAC 7.61A
110VAC 6.90A
115VAC 6.52A
120VAC 6.28A
127VAC 5.90A
200VAC 3.73A
208VAC 3.59A
220VAC 3.37A
230VAC 3.24A
240VAC 3.13A
Table continued on next page