Installation manual

A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 32 © IBM Corporation 2012
Attached 32A 3ph Cord (IEC309 3P+N+G)
IEC-309 3P+N+G 3.0 meter 32A, 3P5W plug (Type 532P6W)
32A (32A / Phase) 380-415VAC Three Phase Wye
96A Total Circuit Capacity
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin &
Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N HBL532C6W
Used with:
46M4143 0U 12 C19/12 C13 Basic PDU
46M4137 0U 12 C19/12 C13 Switched and Monitored
Attached 90A DC line cord (Hardwired)
90A@240-380VDC cable is 4.3 meter with a pig-tail termination (i.e. no plug). It has three stranded copper conductors, each
with a cross section of 25 sq. mm.
The PDU conductors are connected to a high-voltage dc power source as described in the table. All connections must be
performed by a licensed electrician, following local electrical codes or requirements.
Wire color
Function
Green-yellow
Earth ground
Blue
Negative DC Voltage
Brown
Positive DC Voltage
Used with:
44T0966 1U Higher Voltage DC PDU
Male PinFemale Sleeve
EQUIP.
GR.
G
L1
L2
L3
L1
G
L2 L3
N
G
N
L1
L2L3
N
SYS.
GR.
380- 415V
380-415V
380- 415V
220-240V
220- 240V
220- 240V