Installation manual
A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 31 © IBM Corporation 2012
Attached 16A 3ph Cord (IEC309 3P+N+G)
IEC-309 3P+N+G 3.0 meter 16A, 3P5W plug (Type 516P6W)
32A (32A / Phase) 380-415VAC Three Phase Wye
48A Total Circuit Capacity
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin &
Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
Matching receptacle listing 516R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL516R6W
Matching connector listing 516C6W IP-67 HUBBELL, Hubbell connector P/N HBL516C6W
Used with:
46M4122 – 0U 24 C13 PDU
Attached 32A 1ph Cord (IEC309 P+N+G)
IEC 309 P+N+G 3.0 meter (4.3m) - 32A / 220-240VAC Single Phase
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin &
Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
Matching receptacle listing 332R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL332R6W
Matching connector listing 332C6W IP-67 HUBBELL, Hubbell connector P/N HBL332C6W
Used with:
46M4131 – 0U 24 C13 Basic PDU
46M4119 – 0U 24 C13U Switched and Monitored
Male PinFemale Sleeve
EQUIP.
GR.
G
L1
L2
L3
N
SYS.
GR.
380- 415V
380-415V
380- 415V
220-240V
220- 240V
220- 240V
L1
G
L2 L3
N
G
N
L1
L2L3
Male PinFemale Sleeve
G
NL
G
N L
G
EQUIP.
GR.
N
L
220- 240V
220- 240V