Installation manual

A Guide To IBM System x Power Distribution Units (PDU) - International
P a g e | 28 © IBM Corporation 2012
40K9611 - IBM DPI 32A Cord (IEC 309 3P+N+G)
IEC-309 3P+N+G (4.3m) 32A, 3P5W plug (Type 532P6W)
32A (32A / Phase) 380-415VAC Three Phase Wye
96A Total Circuit Capacity
Only a receptacle or a connector is needed to mate with the plug on the PDU input line cord. See section “IEC 309 Pin &
Sleeve Plug Decode” on page 60 in this document for further details on IEC309.
Matching receptacle listing 532R6W IP-67 HUBBELL, Hubbell receptacle P/N HBL532R6W
Matching connector listing 532C6W IP-67 HUBBELL, Hubbell connector P/N HBL532C6W
Used with:
46M4002 1U 9 C19 / 3 C13 Switched and Monitored
46M4004 1U 12 C13 Switched and Monitored
71762MX DPI Ultra Density Enterprise PDU+
71762NX DPI Ultra Density Enterprise PDU
39M2816 DPI Enterprise PDU+ (C13)
39Y8941 DPI Enterprise PDU (C13)
39Y8948 DPI Enterprise PDU (C19)
Re-termination in Australia/New Zealand
The IEC-309 3P+N+G may need to be replaced in AUS/NZ with Clipsal P/N 56PA532 (5 Wire, Three Phase Wye) plug.
Male PinFemale Sleeve
EQUIP.
GR.
G
L1
L2
L3
L1
G
L2 L3
N
G
N
L1
L2L3
N
SYS.
GR.
380- 415V
380-415V
380- 415V
220-240V
220- 240V
220- 240V
Male PinFemale Sleeve
E
L1
L2
L3
Earth
GR.
415V
415V
E
L1
L2
L3
N
415V
SYS.
GR.
240V
240V
240V
N
E
L3
L2
L1
N